KROHNE SU 600 EN User Manual
Page 31

Relay outputs
Quantity
2x operating relay, 1x fail safe relay
Contact
floating spdt
Contact material
AG NI 0.15 hard gold-plated
Turn-on voltage
min. 10 mV DC, max. 250 V AC/DC
Switching current
min. 10 µA DC, max. 3 A AC, 1 A DC
Breaking capacitance
min 50 mW, max. 500 VA, max. 54 W DC
Min. switching hysteresis
0.5 %
Current outputs
Quantity
1x output
Range
0/4 … 20 mA
Resolution
0.1 % or 20 µA
Max. load
500 Ohm
Fault signal
22 mA
Linearity error
0.1 % (relating to 20 mA)
Temperature error
0.01 %/K (relating to 20 mA)
Displays
Measured value indication
- LC display (45x45 mm)
digital and quasianalogue indication
- max. indicating range
-9999 ... 9999
LED displays
- status indication operating vol-
tage
1x LED green
- status indication fault signal
1x LED red
- status indication operating re-
lay 1/2
2x LED yellow
Adjustment
Adjustment elements
2x keys in the front, 1x function switch
Ambient conditions
Ambient temperature
-20 … +60°C (-4 … +140°F)
Storage and transport temperature
-40 … +80°C (-40 … +176°F)
SU 600 - 4 … 20 mA signal conditioning
31
Supplement
30652
-EN
-050525