CAPAFLUX

6

CAPAFLUX

IFC 090 K-CAP Signal converter

Versions
IFC 090 K/B (Standard)

Basic version, without local display and control elements

IFC 090 K/D (Option)

Display version, with local display and control elements

IFC 090 K/D-EEx

Ex version with “Increased Safety” outputs

Interfaces (option)

– HART®
– RS 485/PROFIBUS/FIELDBUS (switch-selectable add-on module)

Add-on equipment (option)

CONFIG-Software and adapter for operator control via MS-DOS PC,
connection to internal IMoCom interface (equipment bus)

Current output
Function

– all operating data configurable
– galvanically isolated from current output and all input circuits
– for active or passive mode

Current:

fixed ranges

0 – 20 mA and 4 – 20 mA

variable ranges

for Q = 0%

I

0%

= 0 – 16 mA

for Q = 100%

I

100%

= 4 – 20 mA

}

adjustable in 1 mA increments

for Q > 100%

I

max

= 22 mA

Active mode

max. 500

Ω load

Passive mode

external voltage:

15 ... 20 V DC

20 ... 32 V DC

load: min ... max.

0 ... 500

250 ... 750

Error identification

0/22 mA and variable

Forward/reverse flow measurement

direction identified via status output

Pulse output
Function

– all operating data configurable
– galvanically isolated from all input and output circuits
– digital pulse division, interpulse period non-uniform, therefore if frequency

and cycle meters connected allow for minimum counting interval:

gate time, totalizer

1000

P100% [Hz]

Active mode

connection: electronic totalizers
voltage: approx. 15 V DC, from current output
load: I

max

< 23 mA, operation without current output

load: I

max

< 3 mA, operation with current output

Passive mode

connection: electronic or electromechanical totalizers
voltage: external, U

ext

≤ 30V DC/≤ 24V AC

load: I

max

≤ 150mA

Pulse width

automatic: pulse duty cycle 1:1, max 1000 pulses/s = 1 kHz

variable: 10 ms – 2 s

P

100%

[pulses/s] = f

max

[Hz] =

1

2 x pulse width

Forward/reverse flow measurement

flow direction identified via status output

Status output (passive)
Function

configurable as measuring range identification for BA mode,
indicator for flow direction, errors or trip point

Connection

voltage: external, U

ext

≤ 30 V DC/≤ 24 V AC

load current: I

max

≤ 150 mA

Control input (passive)
Function

– configurable for range change, totalizer reset, error reset,

set outputs to min. values or hold actual output values

– initiate function by “low” or “high” control signals

Control signals

U

max

: 24 V AC

32 V DC (any polarity)

low:

≤ 1.4 V

≤ 2 V

high:

≥ 3 V

≥ 4 V

Output/input combinations

I = current output P = pulse output S = status output C = control input
The following combinations can be set:
1)

I

P

S

2)

I

P

C

3)

I

C

S

4)

I

S1

S2

5)

I

C1

C2

Time constant

0.2 – 99.9 s, adjustable in increments of 0.1 second

Low-flow cutoff

Cutoff “on” value: 1 – 19%
Cutoff “off” value: 2 – 20%

}

of Q

100%

,

adjustable in 1% increments