Part A System installation and start-up Sect. 2.2

05/2002

IFC 210 E 13

2.2

Pulse output P

•

The pulse output is galvanically isolated from the current output and all input circuits.

•

Setting data and functions can note down in Section 3.3.
Please also refer to Sect. 3.2 Factory settings.


•

Typical pulse output P




P
pulse output



P pulse output

•

All operating data and functions can be set, see Sect. 4 and 5.7, Fct. 1.06 for operator control

•

The pulse output can be operated in the active or passive mode.

•

Active mode:

The current output is the internal voltage source,
connection of electronic totalizers (EC)

•

Passive mode:

External DC or AC voltage source required,
connection of electronic (EC) or electromechanical (EMC) totalizers

Please note:

A fixed pulse width (0.01 – 1s) must be set for operation with EMC
totalizer
. Only then is an optocoupler active for higher output currents.

•

Digital pulse division, interpulse period is non-uniform. Therefore, if frequency meters or

•

cycle counters are connected, allow for minimum counting interval:

1000

•

gate time, counter

≤

P

100%

[Hz]

•

Connection diagrams, see Sect. 2.5: diagrams