Part A System installation and start-up Sect. 2.5

05/2002

IFC 210 E 17

e

Pulsoutput P

activ

for electronic totalizer (EC)

f

Pulsoutput P

passiv

for electronic totalizer (EC) or
electromechanical totalizer (EMC)

U

int

= 22-25 V DC from current output

I

max

3 mA operation with current output I

I

max

23 mA operation without current output I

EMC:

EC:

U

ext

32 V DC /

I

max

150 mA

U

ext

32 V DC

24 V AC

f

50 Hz

I

max

20 mA

Pulses

1 kHz

< 10 kHz

R (load)

1-10 k

1-3

k

R = 10 k

, prevents incorrect counts

when pulse output in open circuit

R = load impedance with EC totalizer operation; for
value refer to table above

Where frequencies are > 100 Hz, use shielded
cables (RFD)

Where frequencies are > 100 Hz, use shielded cables
(RFD)

g

Statusoutput S

activ

(connection to B2 and/or B1)

h

Statusoutput S

passiv

(connection to B2 and/or B1)

U

int

= 22-25 V DC from current output

I

max

3 mA operation with current output I

I

max

23 mA operation without current output I

U

ext

I

max

32 V DC /

24 V DC

150 mA