7.5.2 Limits for supervisor menu functions related to device configuration

CAUTION!

Make sure that:

2.6.1 HART ADDRESS is set to "0". If it is not set to "0", the safety function will not operate
correctly.

2.4.2 RANGE I is set to "4-20 / 3.6E" or "3.8-20.5 / 3.6E". If the error signal is set to "22 mA" or
"Hold", the safety function will not operate correctly.

Menu

No.

Function

Function description

Selection list

Default value

and comments

2.3.1

TANK HEIGHT

The distance from the tank

connecting flange face /

thread stop down to the tank

bottom.

min-max:

0…40 m / 0…131 ft

Default value

agrees with the

customer order

2.4.1

OUTPUT FUNC.

The output function. Select an

output function to scale the

current values in relation to a

given point (usually the device

process connection or the tank

bottom). The output current

value is shown on a bar graph

in normal mode if the

measurement name is the

same as the output function.

Conversion parameters are

shown if there is volume or

mass data in 2.8.1 INPUT

TABLE.

Distance, Level,

Distance conversion,

Level conversion

Default value

agrees with the

customer order

2.4.2

RANGE I

This parameter sets the range

of the output current with

(3.8...20.5 mA) or without

(4...20 mA) over-run values. It

also tells the device what to do

if an error occurs. For

example, the device will

change to an error value of

3.6 mA if you set RANGE I to

"3.8-20.5/3.6E".

4-20, 4-20 / 22E,

4-20 / 3.6E,

3.8-20.5 / 22E,

3.8-20.5 / 3.6E

3.8-20.5 / 3.6E

1

2.4.3

SCALE 4mA

This gives a measurement

value to 4 mA.

min.-max:

2

Default value

agrees with the

customer order

2.4.4

SCALE 20mA

This gives a measurement

value to 20 mA.

min.-max:

2

Default value

agrees with the

customer order

2.4.5

ERROR DELAY

The time after which the

current output changes to an

error value. The error value

shows that there is a

measurement error.

MN=minutes and S=seconds.

0 S, 10 S, 20 S, 30 S,

1 MN, 2 MN,

5 MN,15 MN

0 S

3