Appendix, 2 proof test report form (for copying) – KROHNE OPTIFLEX 2200C SIL User Manual

Page 32

Advertising
background image

10

APPENDIX

32

OPTIFLEX 2200 C

www.krohne.com

01/2013 - 4000738603 - AD SIL OPTIFLEX 2200 R03 en

10.2 Proof test report form (for copying)

For more data, refer to

Proof tests

on page 19.

CAUTION!
Complete the report form that follows when you do a proof test.

Recorded by:

Date:

Unique device ID (e.g. serial number):

Parameter value check

Proof tests results

Recorded value

Correct value

Approved

2.3.1 TANK HEIGHT

Correct tank height

[Yes]

[No]

2.4.3 SCALE 4mA

4.000 mA ± 1 μA

[Yes]

[No]

2.4.4 SCALE 20mA

20.000 mA ± 1 μA

[Yes]

[No]

2.3.3 PROBE LENGTH

Correct probe length

[Yes]

[No]

2.4.2 RANGE I

Error value= 3.6 mA

1

[Yes]

[No]

2.6.1 HART ADDRESS

HART address= 0

2

[Yes]

[No]

1 The error value is correct if the menu item is set to "4-20/3.6E" or "3.8-20.5/3.6E"
2 Multidrop is not permitted for SIL-approved devices

Functional check

Proof tests results

Recorded value

Correct value

Approved

Error alarm signal < 3.6 mA

< 3.6 mA

[Yes]

[No]

Current output= 4 mA

1

4 mA ± 400 μA

[Yes]

[No]

Current output= 12 mA

2

12.000 mA ± 400 μA

[Yes]

[No]

Current output= 20 mA

3

20.000 mA ± 400 μA

[Yes]

[No]

1 The tank is full when menu item 2.4.1 OUTPUT FUNC.= Distance. The tank is empty when menu item 2.4.1 OUTPUT

FUNC.= Level.

2 The tank is 50% full.
3 The tank is full when menu item 2.4.1 OUTPUT FUNC.= Level. The tank is empty when menu item 2.4.1 OUTPUT FUNC.=

Distance.

Conclusion

Does the device operate satisfactorily in safety-related systems?

[Yes]

[No]

Signature: