INTRODUCTION

1

5

OPTIFLEX 2200 C

www.krohne.com

01/2013 - 4000738603 - AD SIL OPTIFLEX 2200 R03 en

1.3 Device description

This device is a 2-wire level transmitter that uses TDR (Time Domain Reflectometry) / Guided
Radar technology. It measures the distance of liquids, liquid gases, pastes, powders, slurries
and granular products.

Measurements are given through a 4...20 mA current output and can be displayed via a DTM
(device type manager) for remote communication or an integrated display screen with wizard-
driven set-up and online help functions. Only the 4...20 mA current output is used as the safety
function.

When the device detects a measurement error, it supplies an output current less than 3.6 mA.
Although the device can be set to a high error value (≥ 21 mA), some hardware failures can cause
the device to give a low error value (≤ 3.6 mA). For more data, refer to

Limits for supervisor

menu functions related to device configuration

on page 17 (2.4.2 RANGE I).

Refer also to "Device description" in the handbook (document [N1]).

1.4 Related documentation

INFORMATION!
The manufacturer designed and developed the device for safety integrity level (SIL) 2.
Data for the SIL approval is not taken from field experience (i.e. it is not

proven in use

) because

this method can give unrealistic data if assumptions are too optimistic.

[N1] OPTIFLEX 2200 Handbook
[N2] IEC 61508-1 to 7:2010 Functional safety of electrical / electronic / programmable

electronic safety-related systems

[N3] NAMUR Recommendation NE 043 Standardization of the Signal Level for the Failure

Information of Digital Transmitters

[N4] NAMUR Recommendation NE 053 Software of Field Devices and Signal Processing

Devices with Digital Electronics

[N5] OPTIFLEX 2200 Supplementary Instructions for ATEX applications