KROHNE ALTOSONIC V Modbus EN User Manual
Page 22

ALTOSONIC V
ModBus Manual 0300 rev07 E
7.30855.35.00
Page 22 of 64
7.2.2
RS485/422 card: PCL-745 S
The current generation RS485/422 card
Dip switch ch1***
: COM 3 Address 3E8 (Krohne Altometer setting)
Dip switch ch2***
: COM4 Address 2E8
JP1***
: Interrupt COM3 IRQ4
JP2***
: Interrupt COM4 IRQ3
JP4***
: Transmit driver enable COM3 always RTS
JP5
: Transmit driver enable COM4 default RTS
JP6***
: Receive COM3 (422 is always on)
JP7***
: Terminator jumper COM3 120
JP8***
: Terminator jumper COM3 always not installed
JP9***
: Receive COM4 (422 is always on)
JP10***
: Terminator jumper COM4 120
JP11
: Terminator jumper COM4 (120 for RS422 mode, not installed for RS485 mode)
***(=Krohne Altometer setting)
NOTE:
JP6 and JP9 are always 422 because the receiver is for both RS485 mode and RS422 mode expected to be enabled for the
UFP-Program.
RS485 mode and RS422 mode for COM4 (Modbus) therefore only differs in set up by:
-
Jumper JP11 not installed (RS485) or installed on 120 (RS422)
-
The external wiring for RS422 and RS485
External wiring PCL745 for Modbus: