ALTOSONIC V

ModBus Manual 0300 rev07 E

7.30855.35.00

Page 25 of 64

7.4

What can go wrong?


When using RS485, check:
•

Are the connections between terminal 1 and 4 made?

•

Are the connections between terminal 2 and 3 made?

•

Is the terminate resistor placed between 1+4 and 2+3 (only if UFP-V is the end of the line).

•

Is the jumper set to 485 and not 422? (else the transmitter will continuously be activated and

destroy received messages)

•

Is the polarity correct? Are the lines by accident swapped?

•

Is the software set to Half Duplex (3.8 MODBUS_UART_HALF_DUPLEX=1)


When using RS422, check:
•

Are both terminator resistors placed at the end of the cable on the TX+, TX- and RX+, RX- lines?

•

Is the jumper on the RS485 card set to 422?

•

Is the software set to Full duplex ((3.8 MODBUS_UART_HALF_DUPLEX=0)?


Other checks:
•

Are the following items correct:
baud rate (3.3 MODBUS_UART_BAUDRATE)
N stop bits (3.6 MODBUS_UART_N_STOPBITS)
parity

(3.7 MODBUS_UART_PARITY)

•

Are both systems in the same mode RTU/ASCII (ASV system = 3.9
MODBUS_TRANSFER_MODE)
?

•

Is the Slave ID (5.3 MODBUS_SLAVE_ID) correct?

•

Notice that RTU requires precise timing specifications, some of the RS485 -> RS232/422

converters perform data buffering and may give problems.
If this is the problem try the ASCII mode (3.9 MODBUS_TRANSFER_MODE).

•

Notice that the Slave device will not give any response when it is addressed with a broadcast

(SlaveID=0).


Extra information:

The UFP-V has extra windows, which provide information about the Modbus communication:

These windows are accessed from the Main Window by function key F10

See also Altosonic-V Operating Manual (chapter RUNTIME WINDOWS)

7.5

How Status Flags are Updated

If the status flags must be self-resetting

Each machine cycle (35 ms) all the error and warning flags are updated with the last machine status.
An active flag will be pending for at least (5.4 FLAG_HOLD_TIME * 35) ms.
An Active Flag may be reset earlier (by writing a zero) than the pending time (5.4 FLAG_HOLD_TIME

* 35 ms), but the next update will be after the pending time.


If the flags must be acknowledged
To activate this mode, the parameter 5.4 FLAG_HOLD_TIME must be set to 0. Each machine cycle

(35 ms) all warning and error flags are updated with the last machine status.

The flags can be reset by:
•

writing a 0 to these flags or

•

writing a 1 to the accompanying acknowledge flag (each status flag has an accompanying

acknowledge flag) or

•

writing a 1 to the acknowledge_all flag

(for host computers with limited free programmable Boolean space).