6.4.2 Test
Use this procedure to test the loop current. « xx » in the illustrations shows that you can change
the value or the parameter. Push the keypad buttons in the correct sequence:
Procedure
Screen
Step
Description
Default screen.
•
[>>>>], [
] and [>>>>].
•
Enter the password: [>
>>>], [Enter], [
], [
]
and [>>>>].
•
[^
^
^
^] to confirm.
•
[
].
•
[>>>>].
•
[>>>>].
•
[
] to decrease the value or [
] to
increase the value.
•
[^
^
^
^] to confirm.
This step sets the loop current value. Make
a selection from 3.5, 4, 6, 8, 10, 12, 14, 16,
18, 20 or 22 mA.
•
[^
^
^
^] 3 times to go back to the default
screen.
The loop current goes back to initial value.