8.6.2 Vessel (tank) height

Fct. 3.1.1 TANKHEIGHT

•

Definition of the tank height for the BM 70 A/P:

Distance between the top edge of the tank fitting and
the lower reference point.

•

The lower reference point is that "point" in the vessel
on which the microwaves emitted by the BM 70 A/P
impinge and from which they are reflected. This can be
the tank bottom (sy mmetrical tank with flat bottom) or
the non-horizontal part of the bottom (e.g. tank with
dished bottom) or an additionally fitted plate. The
BM 70 A/P cannot measure below the lower reference
point (usually a "sump" is left in the tank, see diagram
in Sect. 8.5).

•

Selection of unit, see Sect. 8.6.1.

•

Setting ranges for the tank height BM 70 A (standard):

•

00.50 - 40.00 m

•

0050 - 4000 cm

•

00500 - 40000 mm

•

0019.7 - 1574.74 inch

•

001.64 - 131.22 ft

For BM 70 P: max. 35m / 1377.9 inch / 114.8 ft

•

Depending on the version, it is also possible to set an

upper limit for the tank height (e.g. Wave-Stick: 20 m).
The maximum value can be increased by KROHNE
Service to up to 100 m. (For BM 70 A only)

•

The tank height set at this point is simultaneously the

upper limit of the setting ranges for the following
functions:
- Block distance, Fct. 3.1.2
- Antenna extension, Fct. 3.1.4
- Hysteresis, switching output, Fct. 3.6.4

•

If the tank height is changed to a value greater than 30

m, a new empty spectrum must subsequently be
recorded, see Sect. 8.6.12. (not applicable to BM 70P).

8.6.3 Block distance, antenna type and antenna
extension

Fct. 3.1.2 BLOCKDIST

•

Caked deposits or contamination of the antenna, for

example, can cause faulty measurements directly
below the antenna. The function "block distance" is
used to specify a zone below the flange in which
measurements are not to be carried out.

•

Signals within the block distance are suppressed; a

rise in the level above this limit will result in a
measurement corresponding to a distance = block
distance, when Fct. 3.5.6 BD-DETECT = ON.

•

Unit and setting range: same as Fct. 3.1.1

TANKHEIGHT.

•

Recommended minimum value (see also Sect. 3.3):

- for "Wave-Stick": 200 mm
- for stilling wells and "Wave-Stick SW":
antenna length + 300 mm
- all other versions in storage tanks:
antenna extension + antenna length + 100 mm
- all other versions in process tanks:
antenna extension + antenna length + 200 mm

Fct. 3.1.3 ANTENNA

•

The antenna type is factory-set here.

•

STANDARD (all versions incl. "Wave-Stick SW" but

excl. "Wave-Stick")

•

WAVESTICK (not for "Wave-Stick SW")

•

BM 70 P: only STANDARD setting possible.

Fct. 3.1.4 ANT.EXTENS.
The length of the supplied antenna extension is factory-set
here.

•

Unit and setting range: same as Fct. 3.1.1

TANKHEIGHT.

This setting may only be changed when a longer or shorter
antenna extension is installed. Otherwise faulty measure-
ments may result because the BM 70 A/P allows for this
length when measuring. After changing any antenna
extension, record a new empty spectrum, see Sect. 8.6.12.
When a curved antenna extension is used, only the
vertical component (vertical offset) should be entered
here.
Example (S-shaped extension): Fct. 3.1.4 = 323 mm.

323 mm

300 mm

(Fct. 3.1.4)

(Fct. 3.1.5)

8.6.4 Distance piece

Fct. 3.1.5 DIST.PIECE
The length of any supplied distance piece above the
mounting flange is factory-set here.

•

Setting range: 0 ... 2000 mm

•

Default value: 0 mm

The value of 120 mm should be entered for the high-
temperature version of the flange system.

When a curved antenna extension is used, the horizontal
component of this extension should additionally be entered
(= geometric length of the pipe minus the vertical offset).

Example (see drawing above): Fct. 3.1.5 = 300 mm.