KROHNE BM 70 A_P EN User Manual

Page 47

Advertising
background image

Installation and operating instructions BM 70 A/P

Page: 47

11/00

8.6.7 Display

Fct. 3.2.1 (or Fct. 1.1.1) FCT.DISP.
This function is used to select the measured
variable.

•

LEVEL

•

DISTANCE

•

CONVERSION

•

REFLECTION

}

Measuring range, see Figure in
Sect. 8.5.

If the conversion value is to be displayed, a conver-
sion table must be progra mmed first otherwise a
parameter error will occur.

Fct. 3.2.2 (or Fct. 1.1.2) UNIT.LENGTH
Use this function to select the unit for displaying level and
distance.

•

m

• cm

• mm

•

inch

• Ft

•

PERCENT

• BARGRAPH

The "percent display" refers to the scaling range of current
output I. Therefore the current output must also be set to
level or distance, otherwise a parameter error will occur.
Under "Bargraph", a maximum of 25 segments are
displayed in the form of vertical lines in the first line of the
display (0% = 1 segment, 100% = 25 segments).

Fct. 3.2.3 (or Fct. 1.1.3) UNIT.CONV.
Use this function to select the unit for conversion display.

•

m3

l

litres

•

US Gal

l

GB Gal (Gal = gallons)

•

ft3

l

bbl (petroleum barrels)

•

PERCENT

l

BARGRAPH

•

User Unit (see Fct. 3.2.4)

The "percent display" refers to the scaling range of current
output I. Therefore the current output must also be set to
conversion, otherwise a parameter error will occur.
Under "Bargraph" in the first line of the display a
maximum of 25 segments as vertical lines are displayed
(0% = 1 segment, 100% = 25 segments).

Fct. 3.2.4 USER UNIT
Enter the text for the conversion "user unit" (see Fct. 3.2.3)
here. It consists of a maximum of 10 alphanumeric
characters.

•

Characters assignable to each of the 10 places:

alpha characters A-Z / a-z
numbers 0-9 or
special signs + -
blank characters (= underscore)

Fct. 3.2.5 ERROR MSG.

Use this function to select whether errors are to be
displayed during measurement.

•

NO

Error messages shown only in the error list,
see Sect. 8.8

•

YES

When errors occur during measurement,display
of the measured value will alternate with error
messages.

8.6.8 Current output I

Fct. 3.3.1. FUNCTION I
Use this function to select the measured variable.

•

OFF (= deactivated, the output supplies a constant 4

mA, e.g. necessary for HART

®

Multidrop; Fct. 3.3.2 to

3.3.4 cannot then be selected, i.e. they are skipped
over).

•

LEVEL

•

DISTANCE

•

CONVERSION

•

REFLECTION

•

SW.OUTP. (function and switching threshold are set in

Fct. 3.6).

Fct. 3.3.2 RANGE I
Use this function to define the current in error condition.
E = Error at 2 mA or 22 mA.

•

4-20 mA (hold last measured value when error occurs)

•

4-20 mA/E=2 (min. 3.6 mA for Ex-i output!)

•

4-20 mA/E=22

Fct. 3.3.3 SCALE 4 mA

•

This function does not appear (is skipped over) when

"OFF" is set under Fct. 3.3.1.

•

This function is used for Imin = 4 mA to define the

lower value for level, distance, conversion or reflection
(scaling 4 mA).

•

Setting LEVEL or DISTANCE under Fct. 3.3.1:

Setting range and unit for SCALE 4 mA same as for
Fct. 3.1.1 TANKHEIGHT. If a reference or tank bottom
offset is set, this must be allowed for!

•

Setting CONVERSION under Fct. 3.3.1:

Unit for SCALE 4 mA same as in Fct. 3.2.3
UNIT.CONV. But value must be smaller than the maxi-
mum value in the conversion table.

•

Setting REFLECTION under Fct. 3.3.1:

The setting range for SCALE 4 mA is 0...99.

Fct. 3.3.4 SCALE 20 mA

•

This function does not appear (is skipped over) when

"OFF" is set under Fct. 3.3.1.

•

This function is used für I

max

= 20 mA to define the

upper value for level, distance, conversion or reflection

(scaling 20 mA)

•

Setting LEVEL or DISTANCE under Fct. 3.3.1:

Setting range and unit for SCALE 20 mA as for Fct.
3.3.1 TANKHEIGHT. The value set here should not be
greater than the response threshold. (Response
threshold = tank height (Fct. 3.1.1) - block distance
(Fct. 3.1.2)). If a reference or a tank bottom offset is
set, this must be allowed for!

•

Setting CONVERSION under Fct. 3.3.1:

Unit for SCALE 20 mA same as in Fct. 3.2.3
UNIT.CONV. The value set here must be greater than
that of Fct. 3.3.3, otherwise error during Parameter
Check.

•

Setting REFLECTION under Fct. 3.3.1:

The setting range for I

max

= 20 mA is 1...100.

The value set here must be greater than that of Fct.
3.3.3, otherwise error during Parameter Check.

Application and setting examples: see Sect. 8.5