STANDARD VENT - VERTICAL (CATEGORY I)

IMPORTANT!

VENT PRESSURE MUST BE MAINTAINED

BETWEEN -0.02" W.C. AND -0.04" W.C. AT 24"

(61.0 cm) ABOVE BOILER COLLAR.

• Connection for the appliance exhaust vent to the stack must be as direct as possible. Maximum and minimum venting length
for Category I appliances shall be determined per the latest edition of the National Fuel Code (U.S.) and CAN/CSA-B149.1
Installation Code (Canada).

• The horizontal breaching of a vent must have an upward slope of not less than 1/4 inch per linear foot (2 cm/m) from the boiler
to the vent terminal. The horizontal portion of the vent shall be supported to maintain clearances and to prevent physical damage
or separation of joints.

TABLE 10. STANDARD VERTICAL VENTING (CATEGORY I)

* Extending venting over 70 feet (21.3 m) may require special considerations.

APPLIANCE

CERTIFIED

EXHAUST

MAXIMUM LENGTH

MODEL

CATEGORY

VENTING

VENT SIZE

WITHOUT BAROMETRIC DAMPER

MATERIAL

INCHES (cm)

FEET (m)

TYPE B OR

10”(25.4 cm)

35 Feet (10.7 m) without damper

EQUIVALENT

*70 Feet (21.3 m) max. with damper

1300

TYPE B OR

35 Feet (10.7 m) without damper

1500

EQUIVALENT

12" (30.5 cm)

*70 Feet (21.3 m) max. with damper

1850

TYPE B OR

14"(35.6 cm)

35 Feet (10.7 m) without damper

2100

EQUIVALENT

*70 Feet (21.3 m) max. with damper

TYPE B OR

16" (40.6 cm)

35 Feet (10.7 m) without damper

EQUIVALENT

*70 Feet (21.3 m) max. with damper

I

I

I

I

I000

2500