TABLE 11. STANDARD HORIZONTAL VENTING (CATEGORY III)

STANDARD VENT - HORIZONTAL (CATEGORY III)

WARNING: No substitutions of flue pipe or vent cap material are allowed. Such substitutions would jeopardize the
safety and health of inhabitants.

• A maximum of two elbows can be used on inlet and outlet vent piping respectively. Each elbow is equal to 10 feet (3 m) of
straight pipe.

• Use only special gas vent pipes listed for use with Category III gas burning heaters, such as stainless steel Saf-T-Vent
by Heat Fab, Inc., available from A.O. Smith, 500 Tennessee Waltz Parkway, Ashland City, TN 37015 Phone: 1-800-433-2545
or Fax: 1-800-433-2515. Pipe joints must be positively sealed.

Figure 7.

APPLIANCE

CERTIFIED

EXHAUST

MAXIMUM

MODEL

CATEGORY

VENTING

VENT SIZE

VENT LENGTH

MATERIAL

INCHES (cm)

FEET (m)

STAINLESS

STEEL

1300

STAINLESS

1500

STEEL

1850

STAINLESS

2100

STEEL

STAINLESS

STEEL

III

III

III

III

I000

2500

10”(25.4 cm)

12" (30.5 cm)

14"(35.6 cm)

16" (40.6 cm)

70' (21.3 m)

70' (21.3 m)

35' (10.7 m)

35' (10.7 m)