DIMENSIONS/CAPACITIES DATA

Figure 1.

IMPORTANT!

Refer to "Installation Clearances" section of manual
(page 7) for recommended service clearances prior
to boiler placement.

TOP VIEW

LEFT SIDE

TABLE 2. DIMENSIONAL DATA

A

B

C

D

E

F

Model

Inches

c m

Inches

c m

Inches

c m

Inches

c m

Inches

c m

Inches

c m

GW/GB-1000

14.1

35.8

12.2

31.0

40.3

102.4

31.6

80.3

26.0

66.0

46.8

118.9

GW/GB-1300

24.8

63.0

12.2

31.0

40.3

102.4

31.6

80.3

39.3

99.8

57.3

145.5

GW/GB-1500

30.2

76.7

12.2

31.0

40.3

102.4

31.6

80.3

44.6

113.3

64.3

163.3

GW/GB-1850

27.7

70.4

11.2

28.4

43.0

109.2

32.3

82.0

44.0

111.8

78.3

198.9

GW/GB-2100

31.0

78.7

11.2

28.4

43.0

109.2

32.3

82.0

49.5

125.7

85.3

216.7

GW/GB-2500

38.1

96.8

10.5

26.7

43.0

109.2

32.3

82.0

56.5

143.5

99.3

252.2

Input Rating

Exhaust

Air Intake

REAR VIEW

FRONT VIEW

BTU/Hr.

KW

BTU/Hr.

KW Vent Diameter Diameter

Water Conn.

Gas Inlet

Model

Natural Gas Natural Gas Propane Gas Propane Gas

Inches

c m

Inches

c m

Size

GW/GB-1000

990,000

289.95

990,000

289.95

10

25.4

8

20.3

2 1/2 NPT

2 NPT

GW/GB-1300

1,300,000

380.74

1,300,000

380.74

12

30.5

10

25.4

2 1/2 NPT

2 NPT

GW/GB-1500

1,500,000

439.31

1,500,000

439.31

12

30.5

10

25.4

2 1/2 NPT

2 NPT

GW/GB-1850

1,850,000

541.82

1,850,000

541.82

14

35.6

10

25.4

2 1/2 NPT

2 1/2 NPT

GW/GB-2100

2,100,000

615.04

2,100,000

615.04

14

35.6

12

30.5

2 1/2 NPT

2 1/2 NPT

GW/GB-2500

2,490,000

729.26

2,490,000

729.26

16

40.7

12

30.5

2 1/2 NPT

2 1/2 NPT

TABLE 1: GAS AND ELECTRICAL REQUIREMENT

Manifold Pressure Electrical Characteristics

MODEL

Type of Gas Inches W.C. kPa

Volts/Hz Amperes

GW/GB-1000

thru 2500

NATURAL

3.5

0.87

120/60

30

GW/GB-1000

thru 2500

PROPANE

10

2.49

120/60

30

All Models - Maximum Supply Pressure: 14.0 In. W.C. (3.49 kPa)
Minimum Supply Pressure Natural Gas: 6.0 In. W.C. (1.22 kPa)
Minimum Supply Pressure Propane Gas: 11.0 In. W.C. (2.74 kPa)
Minimum Pressures must be maintained during operating conditions.