Technical data, 5 support for sil-approved devices – KROHNE OPTIWAVE 5200C SIL User Manual

Page 31

Advertising
background image

TECHNICAL DATA

9

31

OPTIWAVE 5200 C

www.krohne.com

02/2013 - 4001906202 - AD SIL OPTIWAVE 5200 R02 en

9.5 Support for SIL-approved devices

If the manufacturer makes a modification that has an effect on the safety function of the device,
the manufacturer will tell you about the modification immediately.

Electrical connections

Power supply

Terminals output - Non-Ex / Ex i:

Terminals output - Non-Ex / Ex i:

Terminals output - Non-Ex / Ex i:

Terminals output - Non-Ex / Ex i:

12…30 VDC; min./max. value for an output of 22 mA at the terminal

Terminals output - Ex d:

Terminals output - Ex d:

Terminals output - Ex d:

Terminals output - Ex d:

16…36 VDC; min./max. value for an output of 22 mA at the terminal

Input and output

Current output

Current output

Current output

Current output

Resolution

±3 µA

Error signal

Low: ≤ 3.6 mA acc. to NAMUR NE 43

Error tolerance

If an error is >2.5% of the output signal, this error has a "dangerous undetected

failure" status.

HART

HART

HART

HART

®

Description

HART

®

protocol via passive current output

1

Point-to-point operation

Yes. Current output = 4 mA. HART

®

Address = 0. Output current data that is

transmitted in less than 1 ms is ignored (this data filter agrees with HART

®

protocol

requirements).

Multidrop operation

Multidrop operation is not permitted because the current output (safety function)

must be set to 4 mA. Thus, the safety function cannot supply data about the device

status.

PROFIBUS PA

PROFIBUS PA

PROFIBUS PA

PROFIBUS PA

Description

Not yet available. This option is not permitted.

FOUNDATION

FOUNDATION

FOUNDATION

FOUNDATION Fieldbus

Fieldbus

Fieldbus

Fieldbus

Description

Not yet available. This option is not permitted.

Modbus

Modbus

Modbus

Modbus

Description

Not yet available. This option is not permitted.

Other data

Other data

Other data

Other data

Response time (errors)

Response time = value given in supervisor menu item 2.4.5 ERROR DELAY

If electrical power is not sufficient for correct operation of the device (worst

conditions for operation), the error is shown in less than 30 seconds.

Diagnostic test frequency

1 time / day (firmware does an auto-diagnostic test)

Approvals and certification

SIL

SIL 2

2

Agrees with IEC 61508:2010 Parts 1 to 7

1 HART® is a registered trademark of the HART Communication Foundation
2 When only one liquid is in the tank