5 saving data, 1 saving procedure – KYORITSU 6305 Instruction Manual User Manual

Page 91

Advertising
background image

KEW6305

7.8

● Indications on each wiring configuration

The following messages are displayed on the screen according to each wiring configuration.

Displayed contents

Wiring(

“

Setting 01”)

Displayed at

Screen1

Screen2

Screen3

Screen4

Upper TIME

Middle WP

1P2W (1ch)

Lower WS

- - -

Upper TIME

TIME TIME

Middle WP

WP1

WP2

1P2W (2ch)
1P3W
3P3W

Lower WS

WS1

WS2

-

Upper TIME

TIME TIME TIME

Middle WP WP1 WP2 WP3

1P2W (3ch)
3P3W3A
3P4W

Lower WS WS1 WS2 WS3

Legend:

TIME

: Elapsed time of integration

WP

: Total active electrical energy

WP1/WP2/WP3 : Active electrical energy per phase
WS

: Total apparent electrical energy

WS1/WS2/WS3 : Apparent electrical energy per phase

7.5 Saving data

When integration or demand measurement starts, the measured data will be saved automatically.
There are two locations where data can be saved.

* SD card

: Max. 511 files can be saved.

* Internal memory

: Max. 4 files can be saved.

Data is saved to a SD card automatically when a SD card has been inserted before turning on the
instrument. If the SD card has not been inserted, data is saved automatically to internal memory.

7.5.1 Saving Procedure

* When a survey is started (manually or automatically) a file is opened.
* Data is saved at the end of each integration interval (“

Setting 09”).

Elapsed time

Recording interval

1 2 3

n-1

n

Start of survey

Data saving point

End of survey

* When the survey is closed (manually or automatically) the file is closed
* All the recorded parameters at each data saving point are saved to one file.

Advertising