Lake Monitors FreeFlow Meter User Manual

Page 6

Advertising
background image

0-5 Vdc Configurations

Device Settings: (Refer to Table 1 for details of this output option.)
1) Using a small flat blade screwdriver, set the

10-position selector switch to position 1.

2) Verify that the 2-position jumper JP1 is shunting pins 2 & 3.
3) Connect the output connector to position A, refer to Figure 1.

Table 1: (Field configurable settings for 0-5Vdc output option)

Configurable Control:

0-5 Vdc Setting:

10 position selector switch

Position 1

2 position jumper JP1

Pins 2 & 3 shunted

Output connector

Position A

Electrical Connection:
Refer to Figure 1

Input Voltage:
The supply voltage must be

between 12 and 35 VDC.
NOTE: The input impedance

(resistance) of the receiving

device must not be lower than

1000 ? or non-linearity may

result. Lower impedances will not damage the transmitter.
1) Connect the positive voltage source (+12 to +35 VDC) to terminal

#1 of the DIN connector or the red wire on the pigt ail.

2) Connect terminal #2 of the DIN connector or the black wire from

the pigtail to the negative side of the DC volt age source.

3) Connect terminal #3 of the DIN connector or the white wire from

the pigtail to the 0-5 VDC input of the receiving device.

4) If the power source does not originate at the receiving device, a

wire will need to be connected between the negative side of the

voltage source and the signal ground of the receiving device.

5) If the circuit is operating correctly, the green LED on the circuit

board will illuminate brightly when power is applied to the unit.

Page 6

0-10 Vdc Configurations

Device Settings: (Refer to Table 2 for details of this output option.)
1) Using a small flat blade screwdriver, set the 10-position

selector switch to position 2.

2) Verify that the 2-position jumper JP1 is shunting pins 2 & 3.
3) Connect the output connector to position A, refer to Figure 1.

Table 2: (Field configurable settings for 0-10Vdc output option)

Configurable Control:

0-10 Vdc Setting:

10 position selector switch

Position 2

2 position jumper JP1

Pins 2 & 3 shunted

Output connector

Position A

Electrical Connection:
Refer to Figure 2

Input Voltage:
The supply voltage must be

between 12 and 35 VDC.
NOTE: The input impedance

(resistance) of the receiving

device must not be lower than

1000 ? or non-linearity may

result. Lower impedances will not damage the transmitter.
1) Connect the positive voltage source (+12 to +35 VDC) to terminal

#1 of the DIN connector or the red wire on the pigt ail.

2) Connect terminal #2 of the DIN connector or the black wire from

the pigtail to the negative side of the DC volt age source.

3) Connect terminal #3 of the DIN connector or the white wire from

the pigtail to the 0-10 VDC input of the receiving device.

4) If the power source does not originate at the receiving device, a

wire will need to be connected between the negative side of the

voltage source and the signal ground of the receiving device.

5) If the circuit is operating correctly, the green LED on the circuit

board will illuminate brightly when power is applied to the unit.