NOSHOK 1800 Series Attachable Loop-Powered Indicator User Manual

Page 10

Advertising
background image

Display

Preferred state of the output

Note

off

Inactive in case of an error

on

Active in case of an error

- Press button 1 to validate the selection. The display shows “

1.Err“ again.

The configuration of the output function is now completed. Depending on the selected output

function you have to make the settings for switching / alarm points. See description in chapter

“Switching points / alarm

-boundaries“ for further information.

Hint: The settings for the switching and alarm points can be made later in an extra menu

(see chapter 5).

5 Switching points / alarm-boundaries

Please note:

The storage of a configuration value will be done by switching to the next configuration value

(via button 1).

When configuration is active and no button is pressed for more than 60 seconds the

configuration will be cancelled. Stored changes will not be lost!
Hint:

The buttons 2 and 3 are featured with a ‘roll

-function‘. When pressing the button once the value

will be raised (button 2) by one or lowered (button 3) by one.

When holding the button pressed for longer than 1 second the value starts counting up or

down, the counting speed will be raised after a short period of time.

- When pressing button 1 for >2 seconds the menu to select the switching points and alarm-

boundaries will be called.

- Depending on the configuration you have made in the “output“ menu you will get different

display values. Please follow the specific chapter for further information.

Description

to select

as output

Output

(out)

see

chapter

no output, device is used as display

no

off

--

2-point-controller

2P

switching function

5.1

3-point-controller

AL

min-/max-alarm,

inverse

5.2

Button2

Button1

Button3