NOSHOK 1800 Series Attachable Loop-Powered Indicator User Manual

Page 12

Advertising
background image

- Press button 1 to validate the delay time. The display shows “

A.dEL“ again.

Example:

You want to have a temperature alarm-monitoring of a greenhouse. The alarm should start

when the temperature rises above 50°C or falls below 15°C. Therefore your settings will be

50°C for the maximum alarm-value “AL.HI“ and 15°C for the minimum alarm-value “AL.Lo“.

The alarm will be starting after the temperature rises above 50°C and stays above 50°C for the

entered delay time or after it had been falling below 15°C and stays below 15°C for the entered

delay time.


Please note that the alarm-outputs are inverted! This means, that the output will be

active when there is no alarm!

Now you finished configuring the alarm adjustment of your device. Press button 1 to finish the

adjustment and to switch over to display the measuring value.

6 Offset- and slope-adjustment

The offset and slope-adjustment function can be used for compensating the tolerance of

the used sensor, resp. for vernier adjustment of the used transducer / transmitter.

Please note:

The storage of a configuration value will be occur by switching to the next configuration

value (via button 1).

When configuration is active and no button is pressed for more than 60 seconds the

configuration will be cancelled. Stored changes will not be lost!
Hint:

The buttons 2 and 3 are featured with a ‘roll

-function‘. When pressing the button once the

value will be raised (button 2) by one or lowered (button 3) by one.

When holding the button pressed for longer than 1 second the value starts counting up or

down, the counting speed will be raised after a short period of time.


- Turn on the device and wait after it finished its built-in segment test.
- Press button 3 > 2 seconds. The device will display “

OFFS“ (Offset).

- Use button 2 and button 3 for setting the desired zero point offset-value.
The input of the offset value are in digits. The value that had been set will be subtracted from the

measured value (see below for further information).

Button2

Button1

Button3

1010 West Bagley Road, Berea, Ohio 44017 P 440.243.0888 F 440.243.3472 www.noshok.com