NOSHOK 1800 Series Attachable Loop-Powered Indicator User Manual

Page 11

Advertising
background image

5.1 2-point-controller

This chapter describes how to configure the switching points as use the device for a 2-point-

controller.

This instruction demands that you selected“

2P“ as your desired output function.

- Press button 1 (when not already done). The device will display “

1.on“ (turn-on-point).

- Use button 2 and button 3 to set the desired value, the device’s output should be turning on.

- Press button 1 to validate your selection. The display shows “

1.on“ again.

- When pressing button 1 again, the device will display “

1.off“ (turn-off-point).

- Use button 2 and button 3 to set the desired value, the device’s output 1 should be turning

off.

- Press button 1 to validate your selection. The display shows “

1.off“again.

Example: You want to control the temperature of a heating coil, with a hysteresis of +2°C,

to 120°C. Therefore you will have to select the turn-on-point “1.on“ to 120°C and

the turn-off-point to “122°C“. When your heating coil temperature falls below 120°C

it will be turned on. When the temperature rises above 122°C the heating coil will

be turned off.

Note:

Depending on the inertia of your heating coil an overshooting of the temperature

may be possible.

Now you finished configuring the switching point adjustment of your device. Press button 1

to finish the adjustment and to switch over to display the measuring value.

5.2 Min-/Max-Alarm

This chapter describes how to configure the device‘s alarm bou

ndaries for min-/max-alarm-

monitoring.

This instruction demands that you selected “

AL“ as your desired output function.

- Press button 1 (when not already done), the device will display “

AL.Hi“.

(maximum alarm-value)

- Use button 2 and button 3 to set the desired value, the device should turn on its

maximum-alarm.

- Press button 1 to validate your selection. The display shows “

AL.Hi“ again.

- When pressing button 1 again, the device will display “

AL.Lo“ (minimum alarm -value).

- Use button 2 and button 3 to set the desired value, the device should turn on its

minimum-alarm.

- Press button 1 to validate your selection. The display shows “

AL.Lo“ again.

- When pressing button 1 again, the device will display “

A.dEL“ (delay of the alarm -function).

- Use button 2 and button 3 to set the desired delay of the alarm-function.
Note:

The selected value [0 ... 9999] accords the alarm delay in seconds.

The device will turn on the alarm after minimum or maximum alarm value was

active for the delay-time you have set.