Grounding Guidelines:

For best results, use a good quality earth ground, such as
metallic water piping, or a stake driven into the ground.

If the flow sensor is installed in metallic piping, for optimum
grounding clamp wires to the piping a short distance to either
side of the flow sensor using hose type clamps. Connect
these wires to the earth ground and to one of the housing
screws. (For non-metallic piping, this step is not needed.)

EX meters are usually unaffected by moderate levels of
electrical noise. In some applications performance may be
improved by taking the following steps:

• Use shielded twisted pair cable (Belden 8723 or

equivalent above ground or Alpha 35482 or

equivalent burial).

• Clamp a ferrite bead (Steward 28A2029-OAO or

equivalent) on meter signal/power wire within 3/4”

of the meter strain relief (tape or tie wrap in place if

necessary). See diagram below.

• IMPORTANT - Connect the cable shield ground wire

to ground, ONLY at power supply end of cable.

General Electrical Guidelines:

• Whenever possible avoid running control cables in

the same conduit with AC power.

• Using shielded cable, be sure that one end is

grounded.

• Avoid routing flow sensor cables in close proximity

to a variable frequency drive.

• Recommended power and output wiring is shielded

18-22 AWG control cable.

• Recommended voltage is 12-24 VDC. Note

that unregulated power supplies can vary from
nameplate voltage by a considerable amount. When
in doubt, use a regulated power supply.

See the Connections diagrams on the following pages for
the appropriate terminals.

Power: A 12 - 24 Vdc power supply capable of at least 250
mA current output is needed.

Forward Flow Output: This open-collector isolated output
does not supply power. It functions like a polarity-sensitive
switch closure. This pulse is generated in the forward flow
direction on the standard unit. (Reverse flow output is
available as an option).
Note: This output is limited to 6 mA at 30 Vdc maximum.

Reverse Flow Output: Reverse flow output is available
as an option. This open-collector isolated output does not
supply power. It functions like a polarity-sensitive switch
closure.
Note: This output is limited to 6 mA at 30 Vdc maximum.

Page 8

ELECTRICAL CONNECTIONS

GROuNDING DIAGRAM

Ground To
Metallic Pipe

Earth
Ground

hose Clamp

(Not needed for non-metallic pipe)

PLACE FERRITE bEAD hERE