5 output signals, Output signals, Table 5: available output types – Spectrex 40/40UFL Ultra Fast UV/IR User Manual

Page 25

Advertising
background image

TM 40/40UFL, Rev (2) August 2013

Performance Considerations

13

1.5.5 Output Signals

Outputs are available according to the default configuration or the wiring
options selected for the 40/40UFL detector. Determine the outputs for your
model according to Table 5.

The detector incorporates several types of output suitable to different
control systems:

0-20mA (stepped) with HART

Relays (Alarm, Fault, Auxiliary)

RS-485 Modbus

Analog Output – analog output proved ultra-fast detection to comply
with 20 msec detection.

Table 5: Available Output Types

Output Type

Version

Detector Status

Alarm relay

Options 1XXXX, 4XXXX,
5XXXX

The relay is N.O.

Options 2XXXX, 3XXXX

The relay is N.O. and N.C.

Auxiliary relay

Options 4XXXX and
5XXXX

The relay is N.O.

Fault relay

Options 1XXXX, 2XXXX,
4XXXX

The relay is N.C. energized

Options 3XXXX, 5XXXX

The relay is N.O. energized

0-20mA
Current Output

Option 1XXXX

SINK Option, (can be
changed to Source – see
Figure 10, Figure 11 and
Figure 12)

Options 2XXXX and
3XXXX

SOURCE Option with the
HART protocol

RS-485

All versions

Modbus protocol

Analog Output

All Versions

0 V during Normal
5 V during detection

Advertising