2 automatic bit, Table 8: results of a successful bit, Table 9: results of an unsuccessful bit – Spectrex 40/40UFL Ultra Fast UV/IR User Manual

Page 29

Advertising
background image

TM 40/40UFL, Rev (2) August 2013

Internal Detector Tests

17

1.6.2.2 Automatic BIT

The detector automatically performs a BIT every 15 minutes. A successful
BIT sequence does not activate any indicator.

All outputs of BIT results function as described in Table 8 and Table 9, and
the BIT is automatically executed every 1 minute. This continues until a
successful BIT occurs, when the detector resumes normal operation.

Table 8: Results of a Successful BIT

Output

Result

Fault relay

Wiring options 1, 2, 4: remains CLOSED

Wiring options 3 and 5: remains OPEN

0-20mA
output

Wiring option 1, 2, 3: Normal (4 mA)

Power LED

Green, Flashing, 1 Hz On (Normal)

Table 9: Results of an Unsuccessful BIT

Output

Result

Fault relay

Wiring option 1, 2, 4: changes to Open

Wiring option 3 and 5: changes to Closed

0-20mA output Wiring option 1, 2, 3: BIT Fault (2mA)
Power LED

Yellow, Flashing, 4 Hz

BIT procedure

Performed every 1 minute

Advertising