Ultra Fast UV/IR Flame Detector User Guide

28

Connecting the Detector

7

Verify the wiring. Improper wiring may damage the detector.

8

Check the wires for secure mechanical connection and press them neatly
against the terminal to prevent them from interfering while closing the
back cover (figure 7).

9

Place and secure the detector’s back cover by screwing the three (3)
socket-head-screws in the Cover Bolts (Figure 4).

2.7.1 Verifying the Detector Wiring

The detector has five output wiring options within the Exde integral terminal
section of the enclosure. There are 12 terminals labeled 1-12.

Table 13 describes the function of each terminal for all the wiring options.
Table 13: Model 40/40UFL Wiring Options

Wire
Terminal
No.

Option 1
Default

Option 2

Option 3

Option 4

Option 5

1

+24 VDC

+24 VDC

+24 VDC

+24 VDC

+24 VDC

2

0 VDC

0 VDC

0 VDC

0 VDC

0 VDC

3

Analog
Output

Analog
Output

Analog
Output

Analog
Output

Analog

Output

4

Fault

Relay N.C.

Fault

Relay N.C.

Fault

Relay N.O.

Fault

Relay N.C.

Fault

Relay N.O.

5
6

Alarm

Relay N.O.

Alarm

Relay N.O.

Alarm

Relay N.O.

Alarm

Relay N.O.

Alarm

Relay N.O.

7

Alarm

Relay C

Alarm

Relay C

Alarm

Relay C

Alarm

Relay C

Alarm

Relay C

8

0-20mA

In

Alarm

Relay N.C.

Alarm

Relay N.C.

Auxiliary

N.O.

Auxiliary

N.O.

9

0-20mA

Out

0-20mA

Out*

0-20mA

Out*

Auxiliary C Auxiliary C

10

RS-485+

(1)

RS-485+

(1)

RS-485+

(1)

RS-485+

(1)

RS-485+

(1)

11

RS-485-

(1)

RS-485-

(1)

RS-485-

(1)

RS-485-

(1)

RS-485-

(1)

12

RS-485

GND

RS-485

GND

RS-485

GND

RS-485

GND

RS-485

GND

*Available with the HART protocol.

Notes:

RS-485 is used for communication network as specified in Appendix C
(Terminals 10, 11, 12) and to connect (in safe area) to PC/Laptop for
configuration/diagnostics.

Alarm relay:

N.O. energized contact in wiring options 1, 4, 5.