Easicool™ precision air conditioning – Airedale EasiCool 6kW 64kW User Manual

Page 21

Advertising
background image

EasiCool™

Precision Air Conditioning

Controls

Password Protection

The control system integrity can be maintained by restricting access with a password PIN number.

CAUTION

IMPORTANT: To change the PIN number, please contact Airedale at time of order with the preferred 4 digit number.

Remote On/Off

Terminals for interlocking are provided to enable or disable the unit remotely.

Fire Shut Down

Terminals for interlocking are provided to shut down the unit in the event of fire.

Evaporator Fan Hours Run Log & Reset

Allows the user to monitor the running times of the evaporator fans and reset after maintenance.

Hours run log or visual service indicator provided.

Filter Change Alarm

Filter change is managed by the AireTronix software, and is based on fan(s) hours run with an alarm being generated
when the pre-set run time limit has been exceeded. The set-point value can be adjusted to suit each application and is
factory set to 4000 hours.

Hours run log or visual service indicator provided.

Standard Network Features

As standard the AireTronix controller is capable of the providing a platform for the following and can be enabled on
request for 2 to 8 units, please specify at order:

Networking

A Local Area Network can be used to connect up to 6 units to offer intercommunication and Duty/Standby control. This
also allows the connection of computers, printers and modems on the same communications ring.
For further details, please contact Airedale Controls.

CAUTION

When adding to an existing network, please consult Airedale to ensure strategy compatibility.

Duty/Standby Operation

The controller enables units to operate in run/standby mode, with up to 6 units networked together, without the need for
additional hardware or controllers. Standby units can be configured to start when the run unit has a critical alarm and/or
a high/low return air temperature alarm.

During peak demand, the standby units can temperature assist.

Duty Rotation

Networked units can be configured to duty rotate, providing equal hours run of fans and compressors.

21

EasiCool Technical Manual 7535768 V1.2.0_02_2013

Introduction

Advertising