Easicool™ precision air conditioning, Technical data upflow, Te ch nic al chi lle d w ate r v – Airedale EasiCool 6kW 64kW User Manual

Page 83: Noise data

Advertising
background image

EasiCool™

Precision Air Conditioning

Sound

Overall

Frequency (Hz) dB

Measurement

dB(A)

63

125

250

500

1000

2000

4000

8000

V28CW

D A

90

102

95

86

84

85

81

81

78

R A

77

87

80

79

74

73

66

60

53

C B

77

87

80

79

74

73

66

60

53

S @ 3m

63

73

65

64

60

59

52

46

39

V31CW

D A

93

105

96

89

86

88

84

84

82

R A

80

90

80

81

76

76

69

63

57

C B

80

90

80

81

76

76

69

63

57

S @ 3m

65

75

65

66

62

61

55

48

42

V35CW

D A

92

111

98

90

87

82

82

83

80

R A

80

96

82

83

78

71

68

63

56

C B

80

96

82

83

78

71

68

63

56

S @ 3m

65

81

67

68

64

56

53

48

41

V40CW

D A

94

113

99

92

89

84

85

85

83

R A

81

98

83

84

80

72

70

65

58

C B

81

98

83

84

80

72

70

65

58

S @ 3m

67

83

69

70

65

58

55

50

44

V45CW

D A

94

113

99

92

89

84

85

85

83

R A

81

98

83

84

80

72

70

65

58

C B

81

98

83

84

80

72

70

65

58

S @ 3m

67

83

69

70

65

58

55

50

44

V50CW

D A

97

115

109

95

92

84

86

84

80

R A

83

98

93

85

82

73

70

63

55

C B

83

98

93

85

82

73

70

63

55

S @ 3m

69

84

78

71

67

59

56

49

40

V55CW

D A

97

115

109

95

92

84

86

84

80

R A

83

98

93

85

82

73

70

63

55

C B

83

98

93

85

82

73

70

63

55

S @ 3m

69

84

78

71

67

59

56

49

40

V60CW

D A

98

116

110

97

93

86

87

86

82

R A

85

101

94

89

84

74

72

66

58

C B

85

101

94

89

84

74

72

66

58

S @ 3m

71

86

79

74

69

60

58

51

43

Technical Data Upflow

Noise Data

Key:
D A

= Discharge Air Sound Power

R A

= Return Air Sound Power

C B

= Case Breakout Sound Power

S @ 3m

= Sound Pressure at 3m

(1)

dB(A) is the overall sound level, measured on the A scale.

(2)

All sound data measured at nominal conditions.

The Sound Pressure data quoted is only valid where the unit is installed on a solid floor (Front and Rear return air only) or false floor (Base return air
only) and against a rear wall. If the equipment is placed adjacent to any other vertical reflective walls, values may vary to those stated, typically
increasing by 3dB for each side added. Values stated do not include for room reverberation conditions.

83

EasiCool Technical Manual 7535768 V1.2.0_02_2013