Electronic controls – Airedale Chilled Water Cassette 2kW - 11kW User Manual

Page 14

Advertising
background image

15

Technical Manual:

6806236 0

/20

CHILLED WATER CASSETTE

To be installed on the wall

or in the electric switch box.

- Manual or automatic speed switch.
- Manual or automatic Summer/Winter switch.
- Electronic thermostat for fan control (ON-OFF).
- Electronic thermostat for valve(s) control (ON-OFF).
- Simultaneus thermostatic control on the valves and fan (ON-OFF).
- It allows control of the low temperature cut-out thermostat TME

(not to be used with TL-E models).

- It allows control of the chilled water valve (ON-OFF) and the electric

resistance in the TL-E version.

- It allows control of the fan and the heating electric resistance.
- It allows control of up to 10 units with SEL-DI speed switch

Note: with 4 pipe installations and continuous chilled and hot water supply, it

allows the automatic summer/winter change-over in accordance to the

room temperature (-1°C = Winter, +1°C = Summer, Dead Zone 2°C).

Identification

Code

TMO - DI

9060521

TMO-DI connection
with 2 valves

TMO-DI connection
with 1 valve

Electronic controls