Technical Manual:

6806236 0

/20

CHILLED WATER CASSETTE

In addition to the air-conditioning units, MaxiNet can also work with
general output cards.
Each card contains 8 outputs which can be connected to “On / Off”
devices.
Inserting a new output card can be done through the regular units
setting.
Handling the existing output cards is done through the output cards’
menu, which can be loaded from the working screen’s menu bar. In the menu, choose the “General Outputs Cards”
title.
The Out-Put card can be connected in a Maxinet network and controlled by the software. Up to 10 cards can be used.

The ETN +/- 3 is a wall-mounted controller that can be connected
to fan coils fitted with the IR electronic board and connected in an
RS 485 network managed by the Maxinet supervisor system. The
controller allows to adjust the set-temperature by raising or lowering
the temperature set, defined with Maxinet, by increments of 1°C
in a range of +/- X°C.

The controller features the following functions:
- switch the appliance on and off
- set the fan speed
- set the range of temperature settings (default +/- 3 °C, modifiable on site up to +/- 9°C)
- modify the set point determined by the MaxiNet system by a value of +/- X°C

The Maxinet system can set the operating mode, the set point and all other operating parameters of the unit, as
well as display the settings made by the user. The Maxinet system always has priority over the ETN controller. For
the correct use of the system, also see the manual for the cassette with remote control and the Maxinet supervision
program.

Accessories MaxiNet

Identification

Code

S08R

9079105

Identification

Code

ETN +/-3°C

9079106