CHILLED WATER CASSETTE

MIN. entering water temperature: + 5°C

MAX. entering water temperature: + 80°C

MIN. entering air temperature: 6°C

MAX. entering air temperature: 40°C

Water flow

Air flow

Supply

MAX. working pressure

8 bar

Suitable relative humidity

15 - 75%

Single phase 230V 50Hz

Installation

MAX. height: See table on page 12

°C

K

20

0.94

30

0.90

40

0.86

50

0.82

60

0.78

70

0.74

80

0.70

°C

K

20

0.94

30

0.90

40

0.86

50

0.82

60

0.78

70

0.74

80

0.70

°C

K

40

1.14

50

1.08

60

1.02

70

0.96

80

0.90

Pressure drop

for mean water temperature of 10°C,

for different temperatures multiply the pressure drop figure

by the K correction factors in the table.

Pressure drop

for mean water temperature of 65°C,

for different temperatures multiply the pressure drop figure

by the K correction factors in the table.

Working conditions

Pressure drop

for mean water temperature of 10°C,

for different temperatures multiply the pressure drop figure

by the K correction factors in the table.

Pressure drop
for cooling battery

Pressure drop
for heating battery

2 pipe installation

4 pipe installation

Water side pressure drop