Technical features, Chilled water cassette, Tl 1.2t model – Airedale Chilled Water Cassette 2kW - 11kW User Manual

Page 4

Advertising
background image

5

Technical Manual:

6806236 0

4/2013

CHILLED WATER CASSETTE

630

4.14

2.96

712

8.8

5.91

508

9.8

33

24

33

0.15

820

5.03

3.65

865

12.5

7.19

618

14.0

40

31

48

0.23

1140

6.34

4.69

1090

18.9

9.10

783

21.4

48

39

77

0.36

710

4.52

3.25

777

10.3

6.45

555

11.5

34

25

42

0.18

970

5.66

4.15

974

15.4

8.10

697

17.4

40

31

63

0.28

1500

7.71

5.83

1326

26.9

11.00

946

29.9

53

44

120

0.53

710

4.52

3.25

777

10.3

6.45

555

11.5

34

25

42

0.18

1280

6.93

5.18

1192

22.1

9.98

858

25.3

48

39

95

0.42

1820

8.89

6.84

1529

34.7

12.70

1092

38.8

58

49

170

0.74

1

2

3

1

2

3

1

2

3

820 x 820 x 303

3.0

1.4

3.0

1.4

3.0

1.4

Speed

Air flow

m

3

/h

Cooling total emission

kW

Cooling sensible emission

kW

Water flow

l/h

¨P Cooling

kPa

Heating

kW

Water flow

l/h

¨P Heating

kPa

Sound power

dB(A)

Sound pressure

*

dB(A)

W

A

Cooling water content

l

Heating water content

l

Dimensions

mm

Fan

MODEL

TL 4.4T

TL 5.4T

TL 6.4T

310

1.51

1.15

260

6.0

1.96

169

6.5

33

24

25

0.11

420

1.96

1.55

337

10.0

2.54

219

10.5

40

31

32

0.15

610

2.33

1.90

401

13.5

3.03

261

14.5

50

41

57

0.27

310

1.85

1.34

318

4.6

2.43

209

5.7

33

24

25

0.11

420

2.36

1.71

406

6.9

3.02

260

8.5

40

31

32

0.15

520

2.70

1.98

464

8.8

3.46

298

10.8

45

36

44

0.20

320

1.85

1.34

318

4.6

2.43

209

5.7

33

24

25

0.11

500

2.65

1.98

456

8.8

3.46

298

10.8

45

36

44

0.20

710

3.34

2.56

574

13.4

4.40

378

16.6

53

44

68

0.32

430

2.36

1.75

406

7.2

3.10

267

8.8

41

32

32

0.15

610

3.02

2.29

519

11.2

3.97

341

13.8

49

40

57

0.27

880

3.81

2.97

655

17.0

4.95

426

20.5

59

50

90

0.45

Speed

Air flow

m

3

/h

Cooling total emission

kW

Cooling sensible emission

kW

Water flow

l/h

¨P Cooling

kPa

Heating

kW

Water flow

l/h

¨P Heating

kPa

Sound power

dB(A)

Sound pressure

*

dB(A)

W

A

Cooling water content

l

Heating water content

l

Dimensions

mm

Fan

1

2

3

1

2

3

1

2

3

1

2

3

575 x 575 x 275

1.0

0.6

1.4

0.7

1.4

0.7

1.4

0.7

TL 0.4T

MODEL

TL 1.4T

TL 2.4T

TL 3.4T

310

1.84

1.35

2.22

316

4.9

4.1

33

24

25

0.11

420

2.34

1.75

2.90

402

7.6

6.3

40

31

32

0.15

520

2.68

2.04

3.35

461

9.7

8.2

45

36

44

0.20

320

2.25

1.57

2.56

387

4.6

3.5

33

24

25

0.11

500

3.34

2.39

3.93

574

9.4

7.3

45

36

44

0.20

710

4.33

3.18

5.23

745

15.1

11.4

53

44

68

0.32

430

2.94

2.08

3.43

506

7.5

6.7

41

32

32

0.15

610

3.88

2.81

4.63

667

12.4

11.2

49

40

57

0.27

880

5.02

3.74

6.17

863

19.7

17.7

59

50

90

0.45

630

4.21

3.03

5.12

724

10.9

6.7

33

24

33

0.15

820

4.91

3.58

6.03

845

14.3

9.9

40

31

48

0.23

1140

6.16

4.59

7.77

1060

21.6

15.1

48

39

77

0.36

710

5.31

3.46

5.61

913

9.4

7.9

34

25

42

0.18

970

6.78

4.48

7.34

1166

14.7

12.4

40

31

63

0.28

1500

9.51

6.48

10.71

1636

26.9

23.0

53

44

120

0.53

710

5.31

3.71

6.13

913

9.4

7.9

34

25

42

0.18

1280

8.45

6.09

10.30

1453

21.8

18.6

48

39

95

0.42

1820

11.10

8.25

14.00

1909

35.6

30.6

58

49

170

0.74

310

1.27

1.01

1.62

219

4.5

4.0

33

24

25

0.11

420

1.63

1.32

2.12

280

7.0

6.0

40

31

32

0.15

610

1.98

1.64

2.64

340

10.0

9.0

49

40

57

0.27

1

2

3

1

2

3

1

2

3

1

2

3

1

2

3

1

2

3

1

2

3

1.4

3.0

4.0

2.1

2.1

4.0

0.8

820 x 820 x 303

575 x 575 x 275

Speed

Air flow

m

3

/h

Cooling total emission

kW

Cooling sensible emission

kW

Heating

kW

Water flow

l/h

¨P Cooling

kPa

¨P Heating

kPa

Sound power

dB(A)

Sound pressure

*

dB(A)

W

A

Water content

l

Dimensions

m

TL 1.2T

MODEL

Fan

TL 2.2T

TL 3.2T

TL 4.2T

TL 5.2T

TL 6.2T

TL 0.2T

* The sound pressure levels apply to the reverberant field of a 100 m

3

room and a reverberation time of 0.5 sec.

2 pipe units. The following standard rating conditions are used:

COOLING
Entering air temperature: + 27°C d.b., + 19°C w.b.
Water temperature:

+ 7/12°C

HEATING
Entering air temperature: + 20°C
Water temperature:

+ 50°C

water flow rate as for the cooling conditions

4 pipe units. The following standard rating conditions are used:

COOLING
Entering air temperature: + 27°C d.b., + 19°C w.b.
Water temperature:

+ 7/12°C

HEATING
Entering air temperature: + 20°C
Water temperature:

+ 70/60°C

Technical features

Advertising