Installation, Preinstallation considerations, Installation 7 – Badger Meter Water Conditioning User Manual

Page 7: Preinstallation considerations 7

Advertising
background image

INSTALLATION

Procedures for installing Recordall Turbo Series meters are essentially the same for all meter sizes Any special instructions

required for the installation or connection of accessory devices such as AMR/AMI technologies or strainers is provided in the

literature for those devices

Figure 1

shows a recommended meter installation

BADGER PLATE

STRAINER AND TURBO

SERIES METERS

COUPLING

ADAPTOR

SERVICE

SADDLE

SHUT-OFF

VALVE

TEST TEE

MINIMUM TWO

PIPE DIAMETERS

DOWNSTREAM

OF TURBO

METER

MINIMUM OF FIVE

DIAMETERS OF

STRAIGHT PIPE

VALVE

(open)

BY-PASS

(PERMANENT OR

TEMPORARY)

UPSTREAM

DOWNSTREAM

Figure 1: Recommended meter installation

Preinstallation Considerations

Before proceeding any further with the installation, first read the instructions in the paragraphs immediately following to

become familiar with the requirements and procedures involved

NOTE:

N

The Recordall Turbo Series meters are designed for operation in HORIZONTAL piping arrangements

• Be sure that the meter flow range and size of the meter coincide with the intended service and demand for water

THE LIFE OF THE TURBO METER WILL BE CURTAILED IF OPERATED AT FLOW RATES HIGHER THAN SPECIFIED.

• The meters are designed for use in cold water service (up to 120° F or 49° C) within the applicable flow requirements

for Turbo meters For use with water at higher temperatures, consult your Badger Meter representative or nearest

Badger Meter regional sales office

• If solid material is present in the water to be metered, a strainer must be installed in the service piping upstream of the

meter The strainer, in addition to protecting the meter from debris in the line, minimizes the effect of velocity profile

distortions or turbulence caused by changes in pipe direction or valving resulting in more accurate registration

• Avoid locating the meter in close quarters Allow sufficient space to permit access for meter reading, testing,

and maintenance

• Because of the need to test large meters periodically to verify their performance, it is recommended that a bypass system

be incorporated into the piping arrangement This will also provide a means of performing periodic cleanout and routine

maintenance without interrupting service to the customer A test port is incorporated in the meter housing and can be

used for field accuracy testing

• The Recordall Turbo Series meter is accuracy and pressure tested prior to shipment, therefore no field adjustments

are required As turbine performance is directly related to the flow conditions of the water stream entering the meter,

upstream fittings and piping changes can adversely affect flow registration For valid registration and proper performance,

consider the following installation considerations:
◊ When installing the meter with a separate plate strainer or integral strainer, a minimum of 5 pipe diameters of straight,

unobstructed pipe is recommended upstream of the meter For optimum protection and accuracy, this straight

pipe spool piece should be installed between the separate strainer and meter (see

Figure 1

) A minimum of 10 pipe

diameters (minimum of 25 pipe diameters for smallest size) of straight unobstructed pipe is recommended upstream

of a meter installed without a plate strainer The deletion of a strainer, however, is not recommended This allows for

dampening of velocity profile distortions caused by elbows, pumps, and dirt traps upstream of the meter Where spiral

flows are created by three dimensional elbows or rotary pumps, additional distance to dampen the effect is beneficial

If a basket or Y-type strainer is used, place it 5 to 10 pipe diameters upstream of the meter to dampen velocity profile

distortions created by this design

User Manual

Page 7