TROUBLESHOOTING GUIDE

Trouble

Remedy

No LCD Display

• Check battery voltage Should be 1 5V DC Replace if low or bad

No Rate or Total

Displayed

• Check connection from meter pickup to display input terminals
• Check turbine meter rotor for debris Rotor should spin freely
• Check programming of flow monitor

Flow Rate Display

Interprets Reading

Constantly

• This is usually an indication of external noise Keep all AC wires separate from DC wires
• Check for large motors close to the meter pickup
• Check for radio antenna in close proximity
• Try disconnecting the pickup from the monitor pig tail This should stop the noise

Flow Rate Indicator

Bounces

• This usually indicates a weak signal Replace pickup and/or check all connections
• Examine K factor

DEFAULT K FACTOR VALUES

Meter Size

Default K factor

Lower Limit

Upper Limit

0 375

20,000

16,000

24,000

0 500

13,000

10,400

15,600

0 750

2750

2200

3300

0 875

2686

2148

3223

1 000

870 0

696 0

1044

1 500

330 0

264 0

396 0

2 000

52 0

41 6

62 0

3 000

57 0

45 6

68 0

4 000

29 0

23 2

35 0

6 000

7 0

5 6

8 0

8 000

3 0

2 4

4 0

10 000

1 6

1 3

2 0