Specifications, Operating the monitor, Specifications 6 – Badger Meter B2800 User Manual

Page 6: Operating the monitor 6

Advertising
background image

SPECIFICATIONS

Power Supply Options

Battery Powered

One D size, 1 5V alkaline battery

Loop Powered

Optional 4-20 mA loop power

Alphanumeric Rate and Total Display

Eight digit, 0 75 inch high numeric display

Eight character, 0 38 inch high alphanumeric display
Fixed or toggle modes of operation for flow rate and totalizer display

Accuracy

±0 1%

Temperature Drift

50 ppm / °C (maximum)

Mounting Classification

Meter Mount

Type 4X enclosure

Remote Mount

Type 4X enclosure

Swivel Mount

Type 4X enclosure

Environmental

Operating Temperature

–22…158° F (–30…70° C)

Humidity

0…90% non-condensing

Inputs

Magnetic Pickup Input

Frequency Range: 0…3500 Hz
Trigger Sensitivity: 30 mV p-p
Over Voltage Protected: ±30V DC

Outputs

Type

Opto-isolated open collector transistor

Maximum Voltage

30V DC

Pulse Width

20 mS/maximum rate 20 Hz

Current (ON state)

0 9V drop @ 5 0 mA or 0 7V drop @ 0 1 mA

Optional

4-20 mA output

Certifications

CSA

Class I, Div 1 Groups C, D; Class II, Div 1 Groups E, F, G

UL

Class I, II, III Div 1 Groups C, D

CE

IEC 61326-1

OPERATING THE MONITOR

The monitor has two modes of operation referred to as the RUN mode and the PROGRAM mode Both the RUN mode and the

PROGRAM mode display screen enunciators confirming the state of the monitor A quick glance at the lower left-hand corner

of the LCD screen will confirm operating status Normal operation will be in the RUN mode To access the PROGRAM mode,

press MENU until the first programming screen is displayed After programming the display with the necessary information, a

lock out feature can be turned on to prevent unauthorized access or changing the meter’s setup parameters

Flow Monitor, B2800 Flow Monitor – Simplified

Page 6

November 2013