WIRING THE F6600 / F6650 SERIES DISPLAYS

(WITH F5140 K-FACTOR SCALER)

The Flo-tech FSC-375, F6202-F, and F6222-F turbines require the F5140 K-Factor Scaler to amplify the millivolt sensor output for transmission
to the F6600 series display. The turbines produce a low level signal so it is important to keep the F5140 K-Factor Scaler as close to the flow
sensor as possible. Close proximity will minimize signal interference and help eliminate erratic readings.
1. Feed the terminal end of the F2832 or F6234 cable through the wire bushing on the F5140. Insert the three-wire (customer supplied)

cable that will be used to bring power and return the output signal to the F6600 series readout. Tighten the wiring bushing.

2. Connect the BLUE wire from the F2832 or the RED wire from the F6234 cable to terminal 5 of the F5140 K-Factor Scaler. Connect the

YELLOW wire from the F2832 or the BLACK wire from the F6234 cable to terminal 6 of the F5140 K-Factor Scaler. See

Figure 2

.

Output

Common

+ 12 VDC

3 Wire Cable

(Customer Supplied)

1

2

3

4

5

6

- OUTPUT

+ OUTPUT

- VIN

+ VIN

8.5 - 30 VDC

TURBINE

PICK UP

INTERNAL

3.6K PULL-UP

RESISTOR

JUMPER

PROGRAMMING

PORT

K-FACTOR SCALER

INPUT 8.5 - 30 VDC

MAX INPUT CURRENT: 18 mA

CABLE ASSEMBLY

F6234-6 6 ft (1.8 m)

F6234-15 15 ft. (4.6 m)

CABLE ASSEMBLY

F2832-6 6 ft (1.8 m)

F2832-15 15 ft (4.6 m)

by

®

K-FACTOR SCALER

F5140

S.N. 12345

2200 South Street Racine, WI 53404 U.S.A.

Phone: 262-639-6770 Fax: 262-639-2267

www.hedland.com

F6600 / F6650

Series Display

COMM

INPUT A.

INPUT B

1 2 3 4 5 6

7 8 9 10 11

+12 VDC

1

2

3

4

5

6

Top of

F6234 Cable

3

2

1

1 - N/C (WHITE)

2 - - (BLACK)

3 - + (RED)

Top of

F2832 Cable

A - + (BLUE)

B - - (YELLOW)

B A

Figure 2: Flo-tech frequency output wiring using F5140 K-factor scaler

4. Connect one of the wires from the customer-supplied cable to terminal 4 (+VIN) of the F5140 and note the wire color. Connect the other

end of this wire to terminal 3 (+12V DC) of the F6600 series display.

5. Connect one of the wires from the customer-supplied cable to terminal 2 (+OUTPUT) of the F5140 and note the wire color. Connect the

other end of this wire to terminal 5 (INPUT A) of the F6600 series display.

6. Connect the remaining wire from the customer-supplied cable to terminal 1 (-OUTPUT) of the F5140. Connect the other end of this wire

to terminal 4 (COMM) of the F6600 series display.

NOTE:

N

A jumper wire is required between terminals 1 and 3 of the F5140.

Signal Wiring, F6600 / F6650 and F6700 / F6750 Series Displays

Page 2

June 2014

SGN-UM-00979-EN-06