Ac or dc power supply, Red black shield (if applicable) series 200 or sdi, Industrial – Badger Meter 330 Series Relay Transmitter User Manual

Page 3: Remote reset, Relay

Advertising
background image

3

Sample Power Supply Wiring Diagram

®

Industrial

Power Out
(+)
(-)
Shield

AC Load/DC +
AC Common/DC -

DIC Comm.

Port

Output

Input

®

Model: 330

SN# 0000000

N.O.

ComA

N.C.

ComB

Hi

GND

Low

DC +

or

AC Load

DC -

or

AC Common

Earth

Ground

AC or DC

Power Supply

Side View - typical Series 300

Removable Connector Wiring

3/32” Flathead

Screwdriver

Series 300

Connector

Wire

Note:
Included with every Series 330 is a Series 330IK kit
containing a screw, lock washer and ground lead to
connect the Series 330 to earth ground. This will help
prevent electrical interference from affecting the Series
330’s normal operation.

Sensor Wiring
All flow sensor types connect to the four terminal header
shown in the “sample sensor wiring diagram.”

If sensor is a Badger

®

Series 200 then:

1) Connect the Red Wire of the sensor to Sensor signal

(+) on the Badger Series 330.

2) Connect the Black wire of the sensor to Sensor signal

(-) on the Badger Series 330.

3) Connect the Bare wire (if applicable) of the sensor to

the Shield terminal on the Series 330.

If sensor is a Badger Series 4000 then:
1) Connect the red wire of the Series 4000 to Power on

the Series 330.

2) Connect the black wire of the Series 4000 to the

Sensor (-) on the Series 330.

3) Connect the clear wire of the Series 4000 to the

Sensor (+) on the Series 330.

4) Connect the bare wire of the Series 4000 to the Shield

on the Series 330.

If sensor is a SDI Series with standard frequency (pulse)

output then:

1) Connect terminal 3 (sensor signal) of the SDI to

Sensor (+) on the Badger Series 330.

2) Connect terminal 2 (sensor common) of the SDI to

Sensor (-) on the Series 330.

3) Connect the terminal 1 (shield) of the SDI to the Shield

on the Series 330.

If sensor is a Non Badger Meter Flow Sensor:
The sensor input power terminal supplies nominal 9.1VDC
excitation voltage for 3 wire sensors. Connect sensor signal
+
and sensor signal - wires to transmitter terminals.

Relay Output Wiring
The Badger Series 330 is supplied with a removable DPST
relay with normally open and normally closed contacts. To
wire to the normally closed contacts connect to the terminals
“NC1” and “NC2”. To wire to the normally open contacts
connect to the terminals “NO1” and “NO2”. Note: this relay
may be used as a Form C relay. Use a jumper to connect
one terminal from each set together as the common
terminal.

Sample Sensor Wiring Diagram

®

Industrial

Power
(+)
(-)
Shield

AC Load/DC +
AC Common/DC -

DIC Comm.

Port

Output

Input

®

Model: 330

SN# 0000000

N.O.

ComA

N.C.

ComB

Hi

GND

Low

Red

Black

Shield

(if applicable)

Series 200

or

SDI

Remote Reset Switch Wiring (if applicable)
The “Hi”, “Com”, and “Lo” terminals on the Badger Series
330 are used for a remote reset. If the remote reset device
provides a momentary dry contact closure - then connect
to the “Lo” and “Com” terminals. If the remote reset device
provides a momentary voltage (up to the supply voltage to
the Series 330) - then connect to the “Hi” terminal.

Remote Reset Location

Power Out
(+)
(-)
Shield

AC L/DC +
AC C/DC -

DIC Comm.

Port

Output

Input

®

Model: 330

SN# 0000000

NO1

NO2

NC1

NC2

Hi

Com

Lo

Remote Reset

Relay Location

Power Out
(+)
(-)
Shield

AC L/DC +
AC C/DC -

DIC Comm.

Port

Output

Input

®

Model: 330

SN# 0000000

NO1

NO2

NC1

NC2

Hi

Com

Lo

Relay