SPEcIFIcatIonS

Power
Power supply options:

12-35 VDC +/- 5%

12-24 VAC +/- 10%
Current Draw:
60 mA @ 12 VDC

Flow Sensor Input
All sensors:
Excitation voltage 3 wire sensors:

7.9 – 11.4 VDC 270W source impedance
Pulse type sensors:
Signal amplitude:

2.5 VDC threshold
Signal limits:

Vin < 35V (DC or AC peak)
Frequency:

0-10kHz
Pull-up:
2 k

W

Sine wave sensors:
Signal amplitude:
10 mV p-p threshold
Signal limits:

Vin < 35V (DC or AC peak)
Frequency:

0-10kHz

temperature Sensor Input
2 required:
10 k

W thermistor, 2 wire, type II, 10 kW @ 25°C

Pulse output
Opto-isolated solid state switch
Operating Voltage range:

0 - ±60V (DC or AC peak)

Closed (on) state:

Load Current - 700mA max. over operating temperature

range

On-resistance - 700mW max. over operating temperature

range

Open (off) state – leakage @ 70°C

<1µA @ 60V (DC or AC peak)

n2 output

RS-485 output compliant with

EIA / TIA - 485 standards

operating temperature

-29° C to +70° C

-20° F to +158° F

Storage temperature

-40° C to +85° C

-40° F to +185° F

Weight

4.8 oz. with headers installed

SEnSor calIBratIon
Badger Meter

Use K and Offset provided in sensor owner’s manual

other Sensors
Check with factory

unItS oF MEaSurE

Flow measurement
Rate:

gpm, gph, l/sec, l/min, l/hr, ft3/sec, ft3/min, ft3/hr, m3/sec,

m3/min, m3/hr

Total:
gallons, liters, cubic feet, cubic meters

Energy measurement
Rate

kBtu/min, kBtu/hr, kW, MW, hp, tons
Total

Btu, kBtu, MBtu, kWh, MWh, kJ, MJ

temperature units
Fahrenheit, Centigrade

ProGraMMInG

Requires PC or laptop running Windows

®

XP or Vista

Badger Meter Model A-302-20 programming kit containing
software and Model A302-20 programming cable