3

HaRdWaRE OVERVIEW
Model 3700 Features and Specifications
Processor

Arm9 embedded CPU, Arm7 io
coprocessor

Operating System

Linux

Flash Memory

16 MB flash

Memory

32 MB ram

LED

8x input, 4 modem activity, Modbus TX/
RX, power, system, IO status

Console

2 x 16 character LCD, two pushbuttons

LAN

RJ45 10/100 Ethernet, full half duplex,
auto polarity

Modem

V.34 bis, 33,600 bps (A8812-1 only)

GSM/GPRS Cellular (A8812-GSM
only)

Protocols

Modbus/RTU, Modbus/TCP, TCP/IP, PPP,
HTTP/HTML, FTP, NTP, XML

Power Supply

24VDC, 1A, class 2 wall brick
transformer.

North America: 110-120VAC, 60hz,
primary. (standard, included)

CE/Europe: 100-240VAC, 50-60hz,
primary, with interchangeable plug
adapters. (optional)

Interval Recording

User selectable 1-60 minutes. Default 15
minute interval

Serial Port1

RS-485 Modbus, supports up to 32
external devices (expandable)

Inputs

1

8 flex-IO inputs with multiple modes:
voltage, current, resistance, pulse and
status.

Voltage mode:

0-10vdc (min/max/average/
instantaneous data)

accuracy: +- 0.25% of full scale at 20°c

Current mode:

4-20mA (min/max/average/
instantaneous data)

accuracy: +- 0.25% of full scale at 20°c

Resistance mode: 100 ohms to 100k.

accuracy:

100

Ω-1kΩ +- 1% of 1kΩ at 20°c

1k

Ω - 10kΩ +- 1% of 10kΩ at 20°c

10k

Ω - 47.5kΩ +- 1% of 47.5kΩ at

20°c

47.5k

Ω - 100kΩ +- 1% of 100kΩ at

20°c

100k

Ω −10MΩ accuracy unrated.

Pulse mode:

intended for use with dry contact outputs.
(consumption/rate/runtime/status)

Standard and KYZ modes for form A and
C relay outputs

Maximum rate: 10hz

Adjustable contact closure threshold:
100

Ω to 10kΩ

Outputs

1

:

2 optically isolated outputs

type: opto-fet, dry contacts.

rating: 30VDC, 150mA max.

Isolation

2

:

The RJ45 ethernet, RJ11 Modem, pulse
outputs, and the primary side of the
power adapter are electrically isolated
from the Model 3700 main PCB board
and inputs.

Environmental

North America: Indoor, temperature
0° - 50°c, 0 - 95% humidity, non-
condensing.

CE/Europe: Indoor, temperature 5° - 40°c,
0 - 90% humidity, non-condensing.

Size

8" x 9.25" x 2.5" (203mm x 235mm x
64mm)

Mass

5lbs (2.3kg)

1

Inputs are intended for low voltage class II outputs.

2

If the product is used in a manner not specified by the

manufacture, the protection provided by the equipment may
be impaired.

electrical Connection

Hardware Installation

Step 1 - Unpack materials: Remove all materials from shipping
box and verify all required components are available

Step 2 - Mount the Model 3700 on the wall or other appropriate
location.

Step 3 - (optional) Connect any analog or pulse output sensors
you may have. For Analog sensors, 0-10V or 4-20mA sensor
types are allowed. The combined power consumption of all the
analog sensors attached to the Model 3700 must not exceed
200mA. If more current is required, use an external power
supply as shown in the wiring diagram for each input type later
in this section.

Step 4 - (optional) - Connect the Modbus network loop as
shown in the wiring diagram on the following page. Follow
the manufacturer’s instructions for installing and powering
the Modbus devices. Verify that the Modbus address settings
are unique for each device (i.e., no two devices with the same
address) and power up the device. Connect each device in the
chain by “daisy-chaining” the devices together. Observe + and
- polarity on the Modbus devices.