Troubleshooting chart, Maintenance, Operation – Blue Angel Pumps BCST50 User Manual
Page 3: Bcap, bcsc, bcsm, bcst, bspm, bspt series
 
3
BCAP, BCSC, BCSM, BCST, BSPM, BSPT Series
www.blueangelpumps.com
Operating Instructions and Parts Manual
• Sump pump will run a minimum of 4
seconds, to a maximum of 16 before 
stopping.
• Sump pump run time will be
determined by the sump pit size and 
water flow rate into the sump pit.
• Under flooding conditions, the
sump pump will stop for 1 second, 
every 16 seconds, and automatically 
turn back on, until water level 
reaches off position of the switch.
Maintenance
Always
disconnect
the
electrical supply before 
attempting to install, service, 
relocate or perform any 
maintenance. If the power 
source is out of sight, lock and 
tag in the open (off) position to prevent 
unexpected power application. Failure to 
do so could result in fatal electrical shock. 
Only qualifi ed electricians should repair this 
unit. Improper repair could result in fatal 
electrical shock.
1. Let the pump cool for a minimum of
two hours before servicing because 
the pump contains hot oil under 
pressure and the motor is hot.
2. Disassembly of the motor prior to
expiration of warranty will void the 
warranty. If repairs are required, see 
troubleshooting chart.
3. Inlet should be kept clean and free
of all foreign objects and inspected 
annually. A clogged inlet will 
damage pump.
4. Pump should be checked monthly
for proper operation.
(BCAP and BCSC Series only)
Pump can be checked for proper operation 
by briefly removing pump power cord 
from the back of the Solid-State Water 
Sensor plug and inserting directly into the 
grounded outlet. In this condition, the 
pump will run continuously. Once pump 
operation is verified, replace pump power 
cord into the back of the Solid-State Water 
Sensor plug (see Figure 5).
Wipe water sensor surface regularly to 
prevent silt or other coatings from building 
up on sensor face (see Figure 5).
This pump contains
dielectric oil for
cooling. This oil can be harmful to the 
environment. Check the state environmental 
laws before disposing this oil.
Troubleshooting Chart
Symptom
Possible Cause(s)
Corrective Action
Pump will not start or 
run
1. Blown fuse, tripped breaker
2. Low line voltage
3. Defective motor
4. Defective float switch
5. Impeller bound
6. Float obstructed
7. GFCI tripped
1. If blown, replace with proper sized fuse or reset breaker.
2. If voltage is under 108 volts, check wiring size.
DO NOT USE AN EXTENSION CORD
3. Replace pump
4. Replace float switch
5. If impeller will not turn, remove housing and remove
blockage
6. Make sure float moves freely up and down float rod
7. Reset GFCI circuit. If GFCI continues to trip, replace the pump.
Pump starts and stops 
too often
1. Back-flow of water from piping
2. Faulty float switch
3. Incoming water is draining on
sensor face
4. Dirty Solid-State Water Sensor
1. Install or replace check valve
2. Replace float switch
3. Position pump switch away from the inlet so switch is
clear from incoming water (see Figure 3)
4. Clean sensor face (see Figure 5)
Pump will not shut off 
or thermal protector 
turns off
1. Incoming water is draining on
sensor face
2. Obstacle in piping
3. Defective float switch
4. Dirty Solid-State Water Sensor
5. Float obstructed
1. Position pump switch away from the inlet so switch is
clear from incoming water (see Figure 3)
2. Remove pump and clean pump, check valve and piping
3. Replace float switch
4. Clean sensor face (see Figure 5)
5. Make sure float moves freely up and down
Pump operates but 
delivers little or no 
water
1. Low line voltage
2. Clogged inlet
3. Plugged impeller
4. Obstacle in piping
5. Check valve installed backwards
1. If voltage is under 108 volts, check wiring size
DO NOT USE AN EXTENSION CORD
2. Clean inlet screen
3. Clean out impeller
4. Remove pump and clean pump, check valve and piping.
5. Reverse position of check valve
Gurgling sound from 
pump at end of cycle
1. Air ingested into pump
2. Time required for pumping is less
than 4 seconds
1. Wipe off surface of sensor (see Figure 5)
2. Additional run time will not damage pump
Operation
(continued)