Electrical data 230v, Electrical data 400v – NORD Drivesystems BU0560 User Manual

Page 4

Advertising
background image

NORDAC SK 500E - ERS Information

Electrical data

4

Subject to technical amendments

BU0560_ERS_GB-0512


The "ERS" special versions are only available for the following devices/powers:

SK

500E-750-323-A-ERS

275410076

SK

511E-750-323-A-ERS

275770076

SK 500E-111-323-A-ERS 275410111

SK

500E-221-323-A-ERS

275410221

SK

511E-221-323-A-ERS

275770221


SK 500E-111-340-A-ERS 275420111
SK 500E-301-340-A-ERS 275420301

Electrical data 230V

Size 1 / 2

Device type:

SK 5xxE…

-750-323-A-ERS

-111-323-A-ERS

-221-323-A-ERS

Nominal motor power
(4-pole standard motor)

230V

0.75 kW

1.1 kW

2.2 kW

240V

1 hp

1½ hp

3 hp

Mains phases

Number

1/3 AC

Mains voltage

200 - 240 V, ±10 %, 47 ... 63 Hz

Output voltage

3 AC

0 - mains voltage

Nominal output current

rms [A]

4.0

5.5

9.0

Min. brake resistor

Accessories

100

 75

 43

Typical input current

1 / 3 AC

rms [A]

8.7 / 5.6

12.0 / 7.7

19.6 / 13.3

Rec. mains fuse

1 / 3 AC

slow-blowing

16 A / 10 A

16 A / 16 A

25 A / 20 A

Type of ventilation

Free convection

Fan cooling, temperature controlled

Switching thresholds: ON ≈ 57°C OFF ≈ 47°C

Weight Approx.

[kg]

1.8

2.7

Electrical data 400V

Size 2 / 3

Device type:

SK 5xxE…

-111-340-A-ERS

-301-340-A-ERS

Nominal motor power
(4-pole standard motor)

400V

1.1 kW

3.0 kW

480V

1½ hp

4 hp

Mains phases

Number

3 AC

Mains voltage

380 … 480 V, -20% / +10 %, 47 ... 63 Hz

Output voltage

3 AC

0 - mains voltage

Nominal output current

rms [A]

3.1

7.5

Min. brake resistor

Accessories

220

 91

Typical input current

1 / 3 AC

rms [A]

4.3 12.5

Rec. mains fuse

1 / 3 AC

slow-blowing

10 A

16 A

Type of ventilation

Fan cooling, temperature controlled

Switching thresholds: ON ≈ 57°C OFF ≈ 47°C

Weight Approx.

[kg]

1.8

2.7


Note:

Up to week of manufacture 48/08, SK 500E-111-340-A-ERS frequency inverters were produced with
free convection (without fan). Since week 49/08 a fan has also been incorporated in units of this size to
provide better dissipation of heat.

Advertising