Derating, Module features, Attention – NORD Drivesystems TI 275271018 User Manual

Page 2

Advertising
background image

POWERLINK Bus module – SK CU4-POL

2

TI 275271018 - 4913

Bus specification

POWERLINK

Max. 100 MBaud

Cable

Min. Ethernet CAT-5

Electrical isolation 500 V

eff

Max. cable length

100 m between two modules

Bus connection

Screw terminals

Shield

Direct to PE

bus termination

performed automatically

PE connection

via PE screw connection

Status display

6 LEDs

in the terminal box

Topology

Star, tree, linear bus

Performance

Update interval for process data between module and frequency inverter

≈ 2.5 ms

Parameter read access on the frequency inverter

≈ 25 ms

Parameter write access with storage in EEPROM

≈ 70 ms

Cycle times

400 µs … 60 ms

Pos : 5 /T ec hnis che Inf or mationen/ SK xU x - Bus - Er wei ter ung en/ Allgemein - Sys temübergreif end/D erating [SK CU 4 - . ..] @ 4\ mod_1378288335408_388. doc x @ 92917 @ 5 @ 1

Derating

ATTENTION

Derating

Depending on the installation location of the module (SK 180E, SK 190E or SK 2xxE), the operating mode (S1,
S3 ...) and the installation type (wall-mounting, motor -mounting) of the frequency inverter as well as the type of
motor used (IE1 / IE2 / ...) restrictions to the permissible ambient temperature must be taken into account. If the
permissible ambient temperature is exceeded, the module may heat up to an impermissible extent and switch off
with an error message (E104.0).

Maximum ambient temperature *

Operating mode

Installation type

SK 180E / SK 190E

SK 2xxE

S1

Motor

25°C

30°C

S3 ED 50 %, 10min

Motor

40°C

n. s.

S3 ED 70 %, 10min

Motor

n. s.

40°C

S1

Wall (unventilated)

37°C

42°C

S1

Wall (ventilated)

47°C

48°C

* The limits of the frequency inverter must not be exceeded (refer to the frequency inverter manual).

Pos : 6 /T ec hnis che Inf or mationen/ SK xU x - Bus - Er wei ter ung en/ Powerlink/M erkmal e [ PO L Allgemei n] @ 3\ mod_1377869060850_388. doc x @ 92057 @ 5 @ 1

Module features

Hot Plugging (CN connection during operation)

Yes

Isochronous (PDO)

Yes, Statistical Mapping

Number of process data

12 Byte (SK TU3-…),
50 Byte (SK xU4-…)

Asynchronous Data (SDO over ASND or UDP/IP)

Yes

Cross Traffic

No, no direct communication between CN

Addressing via

DIP switch, module parameters possible

Access for NORD diagnosis tool via

Diagnostic socket on the device (if available) or possibly
via frequency inverter and UDP Ethernet protocol

Pos : 8 /T ec hnis che Inf or mationen/ SK xU x - Bus - Er wei ter ung en/ Allgemein - Sys temübergreif end/M ont age [ SK CU 4-xxx] @ 3\ mod_1371811235059_388. doc x @ 79455 @ 5 @ 1