NORD Drivesystems TI 275281118 User Manual

Technical information / datasheet, Sk tu4, Attention

Advertising
background image

Technical Information / Datasheet

POWERLINK Bus module

SK TU4-POL

1.1

LED - displays, technical datas, Error 10.9

4913

Rck

TI 275281118

GB

version

reason for change(s)

issue

name

document

speech

Pos : 2 /T ec hnis che Inf or mationen/ SK xU x - Bus - Er wei ter ung en/ Powerlink/SK TU 4-PO L / 275281118 / Basisinf or mationen [SK TU 4-POL] @ 3\ mod_1377869062268_388.doc x @ 92132 @ 555 @ 1

SK TU4

-

POL

Part number: 275 281 118

POWERLINK - External bus interface

ATTENTION

Validity of the documents

This document is only valid in combination with the operating instructions for the relevant frequency inverter.
All of the information that is relevant for a safe start-up of this module and the frequency inverter is only available
under these conditions.

Scope of delivery

1 x

Module

SK TU4-POL

4 x

Hexagon socket

M4 x 40 mm

Accessories required:

1 x

Bus connection unit

SK TI4-TU-BUS

TI 275280000 Part No. 275 280 000)

Field of use

External technology unit for connecting a decentralised frequency inverter (SK 180E … SK 2xxE) to a
POWERLINK field bus. The module can be fitted to or in the immediate vicinity of the frequency
inverter. It is connected to the inverter via the system bus, and can communicate directly with up to 4
frequency inverters. 8 digital inputs and 2 digital outputs are available.

Technical data

Module

Temperature range

-25 °C … 50 °C

Vibration resistance

3M7

Temperature class

Class 3k3

Firmware version

V1.2 R0

Protection class

IP55

Hardware version

AA

Supply voltage

24 V ± 20

%, ≈ 100 mA

Reverse polarity protected

Dimensions [mm]*

H x W x D: 95 x 136 x 99

* module fitted to BUS

-

connection unit

Depth: 108mm with covers on M12

-

connection

Digital input - working area

Low: 0 V … 5 V, High: 15 V … 30 V

Digital input - specific data

R

i

= 8

kΩ, input capacity: 10nF, reaction time 1 ms, inputs

according to EN 61131-2 type 1

Digital output - 24 VDC power supply

≤ 400 mA (input)

Digital output - working area

Low = 0 V, High = 24 V; max. 200 mA

Advertising