Installation, Notice, Sealing – NORD Drivesystems TI 275281206 User Manual

Page 2

Advertising
background image

IO-Extension

– SK TU4-IOE-M12

2

TI 275281206 - 4912

Name

Terminal

Data

Scan rate 1 ms, reaction time 1 ms

Digital output - 24 VDC power supply

35/31

≤ 1000 mA (input)

Digital output - operating range

33.34

Low = 0 V, High = 24 V; max. 500 mA

Analog input - reference voltage

1

10 VDC ±0,1

V, ≤ 20 mA (output)

Analog input - differential input version

3/5; 4/6

Resolution: 12 Bit, accuracy: 0.1 V

Analog output - load capacity

9

≤ 10 mA (Mode: 0/2 … 10 V)
≤ 20 mA (Mode: 0/4 … 20 mA, at 5 V)

Analog output - specific information

9

Resolution: 10 Bit, accuracy: 0.25 V

Pos : 7 /T ec hnis che Inf or mationen/ IO - Er weiter ung/Mont age [SK TU 4-IO E- xxx] @ 2\ mod_1353315135994_388. doc x @ 51251 @ 6 @ 1

Installation

Installation location

on the left or right on the connection unit of the frequency inverter,
alternatively: near to the inverter by means of the SK TIE4-WMK-TU wall-mounting
kit

Fastening

With screw fasteners

NOTICE

Sealing

When installing (module, cable glands, plug connectors), take care that there is a good seal, in order to prevent
the entry of moisture and the danger of corrosion and short circuits. With IP66 modules (SK TI4-TU-...-C) the
membrane valve (supplied) must be screwed in, in order to prevent the accumulation of condensation.

Installation steps for motor installation

1.

Switch off the mains.

2.

Remove the two M25 caps on the required side of the frequency
inverter (right / left).

3.

Remove the printed circuit board (with terminal bar) from the
SK TI4-TU-

…. connection unit.

4.

Install the SK TI4-TU- ... with the enclosed seal on the SK 2xxE
using the 4 enclosed bolts.

5.

Insert both of the enclosed grommets in the M25 cable glands (to
protect the internal wiring between the module and the frequency
inverter).

6.

Replace the printed circuit board (See point 3) and carry out the
electrical connections.

SK TI4-TU-

…-C version devices: remove the top M20 cable gland

(however not at the diagnostic inlet) and insert the enclosed
membrane valve into this screw fitting.

7.

Fit and screw on the SK TU4 module.