Installation, Connections – NORD Drivesystems TI 275900210 User Manual

Page 2

Advertising
background image

IO-Extension

– SK EBIOE-2

2

TI 275900210 - 4612

Name

Terminal

Data

Analog output - load capacity

17

≤ 10 mA (Mode: 0/2 … 10 V)
≤ 20 mA (Mode: 0/4 … 20 mA, at 5 V)

Analog output - specific information

17

Resolution: 10 Bit, accuracy: 0.25 V

RJ45 - current capacity

RJ45 7/8

≤ 1200 mA

Installation

Installation location

Inside a suitable switching cabinet

Mounting

Mounting on snap-on rail (TS 35)

Pos : 8 /T ec hnis che Inf or mationen/ IO - Er weiter ung/Ansc hlüss e [SK EBIO E-2] @ 2\ mod_1353314658836_388. doc x @ 51201 @ 6 @ 1

Connections

Terminals

Screw terminals

6 terminal blocks, each with 4 connections, (5 mm spacing)

Cable cross section

0,14 … 2,5 mm

AWG 14-26

PE connection

via snap-on DIN
rail

The snap-on rail must be earthed

Snap-on rail bus connector

Plug connector

For the serial installation of up to 8 SK EBIOE-2 modules

RJ45

RJ45 - socket

For connection via RJ45 connection cable

Terminal

Contact

Designation

Description

X1
Top
position

40

GND/0V

Reference potential (0 V / GND)

44

VI 24V

Supply voltage (+24 V - in)

78

SYS-

System bus data cable -

77

SYS+

System bus data cable +

X2
Top
position

12

AGND/0V

Analog Ground (internally connected to terminal 40)*

15

AIN2-

Analog input 2, negative

16

AIN2+

Analog input 2, positive

17

AOUT

Analog Out

X3
Top
position

12

AGND/0V

Analog Ground (internally connected to terminal 40)*

13

AIN1-

Analog input 1, negative

14

AIN1+

Analog input 1, positive

11

VO 10V

10 V 
 Reference voltage

X4
Bottom
position

50

VI 24V2

Supply voltage (+24 V - in) for digital outputs

B1

DOUT1

Digital output 1

B2

DOUT2

Digital output 2

20

GND2/0V2

Reference potential (0 V / GND) of digital outputs

X5
Bottom
position

43

VO 24V

Supply voltage for digital inputs (+24 V - out)

C3

DIN3

Digital input 3

C4

DIN4

Digital input 4

40

GND/0V

Reference potential (0 V / GND)

X6
Bottom
position

43

VO 24V

Supply voltage for digital inputs (+24 V - out)

C1

DIN1

Digital input 1

C2

DIN2

Digital input 2

40

GND/0V

Reference potential (0 V / GND)

X7
Front
position

RJ45 - 1

SYS +

System bus data cable +

RJ45 - 2

SYS -

System bus data cable -

RJ45 - 7

GND/0V

Reference potential (0 V / GND)

RJ45 - 8

24 V

Supply voltage (+24 V

– in / out)

X8
Rear
position

Snap-on

rail

bus

connector

Connection of voltage supply and system bus to a further

SK EBIOE

-

2 module

* AGND/0V is internally connected to the reference voltage of the module GND/0V via a special
component. In order to prevent damage to the module or faults in the analog signals, the two contacts
must not be bridged

1 … 8 =

X1 … X8

Advertising