Installation, Danger, Caution – NORD Drivesystems TI 276997120 User Manual

Page 2: Electric shock, Danger of burns, Protection against contact

Advertising
background image

Link circuit choke – SK DCL-950/120-C

2 / 3

TI 276997120 - 1014

Dimensions

Housing dimensions

L x W x H [mm] 146 x 145 x 205

Fastening

L x W [mm]

100 x 95

Connections

No.

Designation

Connection*

Type

Torque

1

Intermediate
circuit

-DC, CP

M8

12.0 Nm

2

Earth lead

PE

M8

12.0 Nm

* Connection cross-section 50 mm²

Electrical data

Number of phases

1

Inductance

mH

0.5 ± 10%

Rated voltage

V =

950

Resistance of windings

mΩ 4.2

Rated current

A =

120

Power dissipation

W

110

Pos : 3 /T ec hnis che Inf or mationen/Dr oss eln/Mont age [Z wisc henkr eisdr oss el - SK 5xxE] @ 4\ mod_1389000368910_388. doc x @ 110111 @ 5 @ 1

Installation

DANGER!

Electric shock

Do not work on live components (observe the 5 safety rules!)

Failure to comply with this will result in serious or fatal injuries in case of contact.

5 safety rules:

• Disconnect
• Secure against switching on
• Check for no voltage
• Earth and short circuit
• Cover or guard adjacent live components

CAUTION

Danger of burns

When in operation, the surface temperature of the device may reach temperatures of approx. 105 °C. To avoid
injury or damage to adjacent components, an adequate minimum distance must be maintained or appropriate
protective devices must be provided.

Installation location

Inside a control cabinet near to the frequency inerter. Note the load bearing
capacity of the mounting plate!

Installation orientation

Floor-standing or on the rear wall of the control cabinet.

Fastening

With screw fastenings

Note

Protection against contact

Adequate protection against accidental contact must be ensured during installation. This protection can, for
example, be by use of the enclosed shrink tube.