NORD Drivesystems TI030_276997071 User Manual

Technical information, Technical characteristics, Area of application

Advertising
background image

 

TI 030 276997071 V1_1   

1/2

 

Technical Information

LINE FILTER SK CIF-323-40

Part No. 276997071

Overvoltage filter – CSA filter

Technical characteristics:

 

Voltage limitation filter pursuant to CSA 22.2 No. 14-5 / UL508C Ch. 48 for reduction of a
5 kV surge pulse (rising edge 1.2 µs/trailing edge 50 µs) to max. 300% of the amplitude
of the rated voltage (230 VAC/240VAC for SK CIF 323 40).

CAUTION!

 

Module SK CIF-323-40 must be used in combination with a suitable mains choke only

(L

min

= 3 x 0.73 mH). The permanent current flowing through the choke must not be less than the

resulting typical input current of the connected frequency inverter(s).

When using a single-phase frequency inverter (SK 2xxE-XXX-123-…) L1 and also L2/N must be

wired to a choke. To do so, you can use a 2-phase (L

min

= 2 x 0.73 mH) or a 3-phase input choke

(L

min

= 3 x 0.73 mH).


Note
With the use of a line choke, the effective input currents of the frequency inverters reduce to
approximately the values of the output currents, depending on inductance and load. Several

frequency inverters can be connected to a choke/filter combination. When doing so, the sum of input

currents must not exceed the rated/nominal current of the filter and/or the choke.

Area of application:

 

Frequency inverter

SK 5xxE-250-323-A … SK 5xxE-112-323-A

SK 2xxE-250-123-A … SK 2xxE-111-123-A

SK 2xxE-250-323-A … SK 2xxE-401-323-A

It is also possible to connect several frequency inverters to an appropriate filter. In this case, the resulting typical input current
(see technical data of FI) is definitive.

Technical parameters:

 

Rated voltage

[V]

1/3~ 200 … 240 ± 10%

Mains voltages

[V]

1/3~ 230 / 1/3~ 240

Rated frequency

[Hz]

47 – 63

Rated current (FLA)

[A]

40 (max.) (input/output current)

max. line fuse

[A]

60*

Weight [kg]

0,74

Protection class

IP 20

Ambient temperature

[°C]

0 … +50

Operating mode

S1 – 100% duty cycle

Certifications

CE; cURus; RoHS

* Class, type and rating of fuse according to connected frequency inverters