Connections, Schematic circuit diagram of electrical connection, Installation data – NORD Drivesystems TI030_276997080 User Manual

Page 2: Scope of delivery, Ul/cul approval, Getriebebau nord gmbh & co. kg

Advertising
background image

 

Getriebebau NORD GmbH & Co. KG

 

Rudolf-Diesel-Straße 1 · D-22941 Bargteheide

Tel.: +49 45 32 - 40 10 · Fax: +49 45 32 - 40 12 53 · www.nord.com

Overvoltage filter

1.0 First

edition

03.11.10

Rck

TI 030 276997080

2/2

1.1

Supplement to UL/cUL approval conditions, tightening torques in lb-in

24.02.12

Rck

Version Change

Date

Name

Document

Page

 

SK CIF-340-30

SK CIF-323-20

SK CIF-340-30

SK CIF-323-20

- Remove fixing screws
- Remove side frames
- Screw on alternate side frames
- Plug fastening elements in

Optional:
Umbau aus Wandmontage
- Befestigungsschrauben lösen
- Seitenteile abnehmen
- Seitenteile für Wandmontage aufsetzen
- Befestigungselemente anstecken

PE (PE2)

L3 (L32)

L2 (L22)

L1 (L12)

PE (PE2)

L3 (L32)

L2 (L22)

L1 (L12)

Frequenzumrichter 2

Netzanschluss -

Frequenzumrichter 1

Netzanschluss -

Inverter 2

Mains supply -

Inverter 1

Mains supply -

NS 35/7,5

- optional for SK CIF-340-30

- optional für SK CIF-340-30

1U2 (L11)

1V2 (L21)

1W2 (L31)

PE (PE1)

Line choke SK CI1-460/x-C

1U1 (L1)

1V1 (L2)

1W1 (L3)

Netzdrossel SK CI1-460/x-C

Befestigungselement
4x für M4

Fastening element

Netz Filter-CSA SK CIF-323-20 / SK CIF-340-30 - Montagehinweise

Line Filter-CSA SK CIF-323-20 / SK CIF-340-30 - Installation hints

Optional:
Modifications for on-wall mounting

Connections:

 

Input and output

Screw/plug-in terminal

0,2 … 4 mm²

L1/L2/L3/PE


Terminal screw tightening torque

0.5 … 0.6 Nm (5 … 7 lb-in)

Schematic circuit diagram of electrical connection:

Installation data:

 

Dimensions:

[mm]

L 180.5 x W 126 x D 71

(Snap-on rail mounting)

L 204,5 x B 126 x T 57

(on-wall mounting)

Scope of delivery:

 

Voltage limitation filter without additional accessories with 4 off removable fastening elements for on-wall mounting.

UL/cUL approval

(supplement to specifications in the frequency inverter manual)

:

 

"Use 75°C Copper Conductors Only"

 

"Connection of copper cable with an insulation rating of at least 75°C"
(only refers to connection cables (mains and motor cables but not control cables)

These products are intended for use in a pollution degree 2 environment"
"The product is suitable for operation in a pollution degree 2 environment"

“Total SCCR of the combination (drive and transient surge suppression device) will be determined by the max. SCCR rating
of the drive according the drive manual or label, type and rating of the Branch Circuit Protection.”, or equivalent. Protection as
described in drive manual, for example type J, T fuses or inverse time trip type circuit breaker.
The total short-circuit current rating of the combination (SK CIF and frequency inverter) is determined by the maximum short-
circuit current rating of the connected frequency inverter. Protection as described in the frequency inverter manual by
approved lead cut-outs or circuit breakers.

Advertising