Getriebebau nord, 3 thermal protection of the motor, 4 three-phase brake motors with a nordac connect – NORD Drivesystems BU6200 User Manual

Page 4: 4 technical data

Advertising
background image

NORDAC connect Operating Instructions

Getriebebau NORD

GmbH & Co. KG
Postfach 12 62
22934 Bargteheide
Tel.: 04532/401-0

⋅ Telefax: 04532/401-555

Änderungen vorbehalten

Specification subject to change without prior notice

Printed in Germany

3.3 Thermal protection of the motor

To protect the motor from overheating, the motor winding is continuously monitored by a thermostat connected
to the terminals TEMP1 and TEMP2. Whenever an overload or overtemperature condition occurs, the NORDAC
connect will switch off the drive automatically.

If the enable signal [RUN] is not removed, the drive will start up again on its own when the
motor temperature has sufficiently decreased.

To prevent the drive from restarting automatically, evaluation of the readiness-for-operation acknowledgement
[OK] signal can be assigned to a control device (PLC).

3.4 Three-phase brake motors with a NORDAC connect

Whenever a three-phase brake motor is combined with a NORDAC connect motor switch, the wiring needed to
connect the brake is taken care of at the factory.
The brakes used have got a coil voltage of 180 V DC. They are connected to terminals BR1 and BR2 .

4 Technical data

NORDAC connect

Power terminals

Mains voltage

3 AC 380 V ... 440 V

±10%, 47 to 63 Hz

Mains current

0.5...8.0 A

(kW)

0.25...3.0

Motor rating

4-pole three-phase standard
motor

(hp)

1

/

3

...4

Control terminals

Supply voltage

U

24V

I

24V

I

24V

19 V...30 V
< 50 mA + I

OK

< 1A (short-circuit)

Control input (RUN)

U

RUN(AUS)

U

RUN(EIN)

0...5 V, I

RUN

< 2 mA

15..30 V, I

RUN

< 20 mA

Output (OK)

OK

Overtemperature

U

OK

(high)

U

OK

(low)

I

OK

(max)

U

24V

high-impedance
0...0,68A (short-circuit)

Type of enclosure:

IP55

Ambient temperature:

-10

o

C to +50

o

C

Advertising