Floor temperature limits (af mode only) – Ouellet TH115 User Manual

Page 14

Advertising
background image

Owner’s Guide

12

ENG

LISH

WARNING: To avoid damaging your floor, follow your floor supplier’s recommendations regarding floor tempera-
ture limits.
The minimum and maximum floor temperature limits are 5.0°C (41°F) and 28.0°C (82°F) by default.
To modify these limits, proceed as follows:

n

Switch the thermostat to Off.

o

Press and hold the

button.

p

Switch the thermostat back to On.

q

Release the

button when the minimum temperature limit (FL:LO) appears.

r

Set the minimum temperature limit using the

buttons.

s

Press the

button to display the maximum temperature limit (FL:HI).

t

Set the maximum temperature limit using the

buttons.

u

Press Mode/Ret to return the thermostat to normal display.

NOTE: The thermostat will automatically return to normal display if no button is pressed for 60 seconds.

Floor temperature limits (AF mode only)

400-115-051-B (Honeywell TH115-AF-GA_GB) 5 x 3.125 EFS.book Page 12 Monday, April 12, 2010 3:10 PM