ROTRONIC ATEX User Manual

Page 10

Advertising
background image

10

Safety Instructions:

Note:
This symbol points to an information which contains important instructions concerning the operating. Inter-
ferences may result, if these are not followed.

Attention:
This symbol points to an information, whose non-observance may lead to serious material damages.
The safety instructions must be strictly observed.


A

Important notice for installation:
Installation in gas atmosphere:
Zone 0:

Only the probe tube respectively the screw-in probe may be in zone 0

Temperature class T5

Zone 1:

The whole transmitter may be in Zone 1

Temperature class T6 for gas atmosphere

Installation in dust atmosphere
Zone 20:

The probes must only be used with the factory-mounted steel sinter filter

Zone 21

The whole transmitter may be in zone 21

Zone 0/20

Zone 1/21

T5 T6
Class ll, Division1
Group E,F,G

Zone 1/21
T6
Class l, Division1
Group A, B, C, D

Safe zone

Zener barrier

In zone 20/21,
only the sinter filter
must be used.

In zone 21,

only the sinter filter

must be used.

HygroClip IC-1-EX

ll 1 G EEx ia llC T5 resp. ll 2 G EEx ia lC T6
II 1/2 D IP6X T 80°C

HygroClip IE-1-EX

ll 1 G EEx ia llC T5 resp. ll 2 G EEx ia lC T
II 1/2 D IP6X T 80°C

HygroClip ID-1-EX

ll 1 G EEx ia llC T5 resp. ll 2 G EEx ia lC T
II 1/2 D IP6X T 80°C

HygroClip IW-1-EX

ll 1 G EEx ia llC T5 resp. ll 2 G EEx ia lC T6
II 2D IP6X T 80 °C